2007-12-11 10:48:36 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| COMMENTS FROM PREVIOUS LIST, NOT ADDRESSED: |
| |
| 1.PROVIDE A REASONABLE VALUATION FOR THIS JOB. |
| |
| 2.COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR |
| PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN |
| ANOTHER FORMAT, FBC*106.TWO SETS REQUIRED. |
| |
| 3.PRESTORM SHUTTER INSTALLATION PLAN PENDING. |
| |
| 4-5.ADDRESSED. |
| |
| 6.PLEASE ADDRESS THE USE OF THE WORDS "ARCHITECTURE" |
| AND "INTERIOR DESIGN".AN INDIVIDUAL LICENSE IS |
| REQUIRED, FS481.A SET HAS BEEN RETAINED AND MAY BE |
| FILED WITH A COMPLAINT TO FBPE AND FLORIDA BOARD OF |
| ARCHITECTS.DOCUMENTS PREPARED BY AN ARCHITECT OR |
| INTERIOR DESIGNER AND SUBMITTED FOR PUBLIC RECORD ARE |
| TO BE SIGNED, SEALED, DATED ORIGINALS FS481. |
| |
| IT APPEARS THAT, DESPITE WARNINGS FROM AND |
| CONVERSATIONS WITH TWO DIFFERENT REVIEWERS ON TWO |
| SEPARATE PROJECTS REGARDING THIS ISSUE, CONTRACTOR IS |
| STILL USING "ARCHITECTURE" AND "INTERIOR DESIGN" |
| WITHOUT A LICENSE.CONTRACTOR STILL SHOWS THIS NAME |
| WITH THE DBPR WEBSITE, HAS USED THIS NAME ON |
| LETTERHEAD, AND MAINTAINS AN ACTIVE CORPORATION. |
| CONTRACTOR'S AGREEMENT WITH THE PLAN REVIEWERS WAS TO |
| DISCONTINUE USE OF THE TERMINOLOGY OR THE MATTER WOULD |
| BE FORWARDED TO FLORIDA BOARD OF ARCHITECTS.THIS |
| COMMENT DOES NOT APPEAR TO HAVE BEEN ADDRESSED. |
| |
| 7.ADDRESSED. |
| |
| 8.SEE FBC1025.4.1 AND SHOW COMPLIANCE ON THE PLAN. |
| |
| THE ENGINEER HAS A STATEMENT ON THE PLAN, "2 EXIT DOORS |
| IN EACH ROOM, NO EGRESS WINDOWS REQUIRED".THE "EXIT |
| DOORS" DO NOT QUALIFY AS EXITS, SEE FBC1002 |
| DEFINITIONS.SEE FBC EB 505, YOU CANNOT REDUCE THE |
| LEVEL OF SAFETY FOR MEANS OF EGRESS UNLESS IT COMPLIES |
| WITH FBC CHAPTER 10.AS WINDOWS FOR EMERGENCY RESCUE |
| IS REQUIRED, FBC1033.6 AND FBC1025.4.1, YOU ARE |
| REDUCING THE LEVEL OF SAFETY BY INSTALLING HURRICANE |
| SHUTTERS. |
| |
| 9--10.ADDRESSED. |
| |
| 11. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED IN |
| ADDITION TO THE NOAS SUBMITTED, FAC9B72, |
| WWW.FLORIDABUILDING.ORG. |