Plan Review Notes
Plan Review Notes For Permit 07100789
Permit Number 07100789
Review Stop B
Sequence Number 2
Notes
Date Text
2007-12-11 10:48:36****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS LIST, NOT ADDRESSED:
  
 1.PROVIDE A REASONABLE VALUATION FOR THIS JOB.
  
 2.COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR
 PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT, FBC*106.TWO SETS REQUIRED.
  
 3.PRESTORM SHUTTER INSTALLATION PLAN PENDING.
  
 4-5.ADDRESSED.
  
 6.PLEASE ADDRESS THE USE OF THE WORDS "ARCHITECTURE"
 AND "INTERIOR DESIGN".AN INDIVIDUAL LICENSE IS
 REQUIRED, FS481.A SET HAS BEEN RETAINED AND MAY BE
 FILED WITH A COMPLAINT TO FBPE AND FLORIDA BOARD OF
 ARCHITECTS.DOCUMENTS PREPARED BY AN ARCHITECT OR
 INTERIOR DESIGNER AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED, DATED ORIGINALS FS481.
  
 IT APPEARS THAT, DESPITE WARNINGS FROM AND
 CONVERSATIONS WITH TWO DIFFERENT REVIEWERS ON TWO
 SEPARATE PROJECTS REGARDING THIS ISSUE, CONTRACTOR IS
 STILL USING "ARCHITECTURE" AND "INTERIOR DESIGN"
 WITHOUT A LICENSE.CONTRACTOR STILL SHOWS THIS NAME
 WITH THE DBPR WEBSITE, HAS USED THIS NAME ON
 LETTERHEAD, AND MAINTAINS AN ACTIVE CORPORATION.
 CONTRACTOR'S AGREEMENT WITH THE PLAN REVIEWERS WAS TO
 DISCONTINUE USE OF THE TERMINOLOGY OR THE MATTER WOULD
 BE FORWARDED TO FLORIDA BOARD OF ARCHITECTS.THIS
 COMMENT DOES NOT APPEAR TO HAVE BEEN ADDRESSED.
  
 7.ADDRESSED.
  
 8.SEE FBC1025.4.1 AND SHOW COMPLIANCE ON THE PLAN.
  
 THE ENGINEER HAS A STATEMENT ON THE PLAN, "2 EXIT DOORS
 IN EACH ROOM, NO EGRESS WINDOWS REQUIRED".THE "EXIT
 DOORS" DO NOT QUALIFY AS EXITS, SEE FBC1002
 DEFINITIONS.SEE FBC EB 505, YOU CANNOT REDUCE THE
 LEVEL OF SAFETY FOR MEANS OF EGRESS UNLESS IT COMPLIES
 WITH FBC CHAPTER 10.AS WINDOWS FOR EMERGENCY RESCUE
 IS REQUIRED, FBC1033.6 AND FBC1025.4.1, YOU ARE
 REDUCING THE LEVEL OF SAFETY BY INSTALLING HURRICANE
 SHUTTERS.
  
 9--10.ADDRESSED.
  
 11. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED IN
 ADDITION TO THE NOAS SUBMITTED, FAC9B72,
 WWW.FLORIDABUILDING.ORG.