2007-11-03 06:00:53 | BUILDING PLAN REVIEW | | PERMIT: 07100778 | | ADD: 701 S. ROSEMARY AVE 1ST FLOOR | | CONT: HOOVER CANVAS | | TEL: (561)768-3508 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW: 1ST | | ACTION: DENIED | | | | 1)FBC 3105.1.1.1NO RIGID PART OF THE AWNING FRAME | | SHALL BE LESS THAN 7 FEET, 6 INCHES FROM THE GRADE | | DIRECTLY BELOW AND NO PART OF THE CLOTH DROP SHALL BE | | LESS THAN 7 FEET. INDICATE ON THE PLANS THE HEIGHT OF | | THE AWNING FROM THE FINISH GRADE TO THE BOTTON ON THE | | FRAME. | | | | 2)FBC 106.1.1 CONSTRUCTIION DOCUMENTS SHALL BE OF | | SUFFICIENT CLARITY TO INDICATE THE LOCATION,NATURE AND | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | WILL CONFORM TO THE PROVISIONS OF THE CODE AND RELAVANT | | LAWS AND ORDINANCES. THE DRAWINGS SHALL INDICATE | | CLEARLY WHERE ON THE BUILDING THE AWNINGS WILL BE | | INSTALLED. | | | | 3)SEE THE ZONING REQUIREMENTSIN PACKAGE. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | (561)805-6726 | | [email protected] |
|