2007-11-06 07:14:072004 FBC W/2007 REVISIONS
 CONSTRUCT A FREE STANDING DECK
  
 DENIED BY BUILDING
  
 1) 2004 FBC 106.1.1 CITY AMENDMENTS INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND REVELENT
 LAWS, ORDINANCES, AND RULES AND
 REGULATIONS AS DETERMINED BY THE
 BUILDING OFFICIAL. THE PLANS THAT WERE SUBMITTED DO NOT
 PROVIDE ENOUGH INFORMATION.SPECIFY THE SIZES OF ALL
 WOOD FRAMING MEMBERS (POSTS, BEAMS, JOISTS, ETC.)
  
 2) SHOW COMPLIANCE WITH R301.1 DESIGN. BUILDINGS AND
 STRUCTURES, AND ALL PARTS THEREOF, SHALL BE CONSTRUCTED
 TO SAFELY SUPPORT ALL LOADS, INCLUDING DEAD LOADS, LIVE
 LOADS, ROOF LOADS, FLOOD LOADS AND WIND LOADS AS
 PRESCRIBED BY THIS CODE. THE CONSTRUCTION OF BUILDINGS
 AND STRUCTURES SHALL RESULT IN A SYSTEM THAT PROVIDES A
 COMPLETE LOAD PATH CAPABLE OF TRANSFERRING ALL LOADS
 FROM THEIR POINT OF ORIGIN THROUGH THE LOAD-RESISTING
 ELEMENTS TO THE FOUNDATION.
 PROVIDE FOUNDATION DETAILS. SPECIFY THE DEPTH THAT THE
 POSTS WILL BE BELOW GRADE AND HOW THEY WILL BE
 ANCHORED. PROVIDE DETAILS OF THE CONNECTIONS OF THE
 BEAMS TO THE POSTS, THE JOISTS TO THE BEAMS AND THE
 DECKING TO THE JOISTS.
  
 3) IF THE DECK IS MORE THAN 30 INCHES ABOVE GRADE
 GUARDS WILL BE REQUIRED. SHOW COMPLIANCE WITH R312.1
 AND R312.2 FOR GUARD RAILS NOT LESS THAN 36 INCHES IN
 HEIGHT WITH INTERMEDIATE RAILS OR ORNAMENTAL CLOSURES
 WHICH DO NOT ALLOW THE PASSAGE OF A SPHERE 4 INCHES IN
 DIAMETER.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW