Plan Review Notes For Permit 07100768 |
Permit Number |
07100768 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-11-07 17:02:21 | 2004 FBC W/2007 REVISIONS | | CONSTRUCT A PEDESTRIAN BRIDGE | | | | 1) SPECIFY THE APPLICABLE BUILDING CODE AND DESIGN | | PARAMETERS ON THE PLANS. FBC 106.1.1 | | | | 2)SPECIFY THE WINDLOAD DESIGN DATA ON THE PLANS. FBC | | 1603.1.4 | | | | 3) SPECIFY THE UNIFORM LIVE LOAD FOR WHICH THE BRIDGE | | IS DESIGNED (MIN. 60 PSF). FBC 1607.3 AND TABLE 1607.1 | | | | 4) SPECIFY THE DESIGN LOADS FOR THE HANDRAILS AND | | GUARDS. FBC 1607.7 | | | | 5) SHOW COMPLIANCE WITH FBC 11-4.1.2 AND 11-4.3 FOR | | ACCESSIBLE ROUTES. | | | | 6) SHOW COMPLIANCE WITH FBC 11-4.3.7 SLOPEAND FBC | | 11-4.8 RAMPS. | | | | - ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|