Plan Review Notes For Permit 07100754 |
Permit Number |
07100754 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-11-07 09:04:50 | DENIED | | REFERENCE: | | ** FBC-2004 WITH 05 & 06 REVISIONS, SECTIONS 424.2 & | | R4101 SWIMMING POOLS. | | ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING. | | ** FBC-2004 CHAPTER 1, THE CITY OF | | WEST PALM BEACH AMENDMENTS. | | ** FLORIDA ADMINISTRATIVE CODE (FAC). | | ** FLORIDA STATUTES (FS). | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | 1) PERMIT APPLICATION IS INDICATING AN ELECTRIC POOL | | HEATER, SHEET 1, POOL EQUIPMENT IS INDICATING A 400,000 | | BTU GAS POOL HEATER. PLEASE CLARIFY AND CORRELATE WHICH | | TYPE OF POOL HEATER IS BEING USED ON THE RESUBMITTAL. | | PER * 106.1.1, INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | 2) FBC-2004 SEC. 424.2.14.1, OR | | FBCR-2004 SEC. R4101.14.1 SWIMMING POOL | | WATER HEATERS SHALL BEAR THE LABEL OF A | | RECOGNIZED TESTING AGENCY. (MANUFACTURE | | SHEETS REQUIRED, PLEASE SUBMIT) | | | | 3) FBC-2004 SEC. 424.2.14.2, OR | | FBCR-2004 SEC. R4101.14.2 WATER | | RETENTION, PROVIDE A POSITIVE MEANS OF | | RETAINING WATER IN THE HEATER WHEN PUMP | | IS SHUT OFF.(MANUFACTURE SHEETS | | REQUIRED, PLEASE SUBMIT) | | | | END OF COMMENTS: | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL: [email protected] |
|