Plan Review Notes
Plan Review Notes For Permit 07100754
Permit Number 07100754
Review Stop P
Sequence Number 1
Notes
Date Text
2007-11-07 09:04:50DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, SECTIONS 424.2 &
 R4101 SWIMMING POOLS.
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1) PERMIT APPLICATION IS INDICATING AN ELECTRIC POOL
 HEATER, SHEET 1, POOL EQUIPMENT IS INDICATING A 400,000
 BTU GAS POOL HEATER. PLEASE CLARIFY AND CORRELATE WHICH
 TYPE OF POOL HEATER IS BEING USED ON THE RESUBMITTAL.
 PER * 106.1.1, INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2) FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
  
 3) FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF.(MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT)
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER