Plan Review Notes
Plan Review Notes For Permit 07100612
Permit Number 07100612
Review Stop B
Sequence Number 1
Notes
Date Text
2007-10-22 15:50:08****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)INDICATE WHICH FASTENING OPTION(S) YOU ARE USING.
 THE PRESSURE OF -55 PSF IS NOT COMPLIANT FOR ZONES 2
 AND 3.SEE PRODUCT APPROVAL, SHEET 2.
  
 2.)PLEASE REMOVE THE MIAMIDADE INFORMATION AS IT IS
 NOT APPLICABLE FOR THIS JOB.CITY OF WEST PALM BEACH
 IS NOT IN THE HIGH VELOCITY HURRICANE ZONE.
  
 3.)PROVIDE TWO SETS OF SPECIFICATIONS FOR THE
 SECONDARY WATER BARRIER. TWO COMPLETE COLLATED SETS ARE
 ALWAYS REQUIRED FOR PERMIT ISSUANCE.
  
 4.)SEE ROOF POLICY REGARDING INFORMATION REQUIRED FOR
 REROOF PERMITS.REVISE THE APPLICATION TO INCLUDE THE
 MEAN ROOF HEIGHT.