Plan Review Notes
Plan Review Notes For Permit 07100611
Permit Number 07100611
Review Stop P
Sequence Number 1
Notes
Date Text
2007-11-02 13:05:44DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. MORE INFORMATION IS REQUIRED DUE TO THE FACT THAT A
 PLUMBING PERMIT HAS BEEN APPLIED FOR PROPOSED PLUMBING
 TO A NEW LAUNDRY BOX. PLEASE PROVIDE THE FOLLOWING
 INFORMATION AS IT PERTAINS TO YOUR JOB.
  
 *** IF THE NEW PROPOSED PLUMBING FLOOR PLAN LAYOUT IS
 DIFFERENT FROM THE EXISTING FLOOR PLAN LAYOUT PLEASE
 SUBMIT THE FOLLOWING INFORMATION ON SEPERATE DRAWINGS.
  
  
 A) EXISTING FLOOR PLAN LAYOUT.
  
 B) NEW PROPOSED FLOOR PLAN LAYOUT AND PLEASE FOLLOW
 WHAT IS REQUIRED IN COMMENT #2.
  
 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS OF THE PROPOSED PLUMBING TO THE NEW LAUNDRY
 BOX IS REQUIRED.
  
 3. THE FOLLOWING INFORMATION IS REQUIRED FOR THE
 PROPOSED PLUMBING TO THE NEW LAUNDRY BOX
  
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
  
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING.
  
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 **NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE THREE
 INCH (3").
  
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 **NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE
 LOCATED AT FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.).
  
 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 **NOTE: PLEASE REFERENCE THE EXAMPLE SANITARY ISOMETRIC
 RISER DIAGRAM ATTACHED TO THE PLUMBING COMMENTS THAT
 REFLECTS THE FLOOR PLAN AND IS CODE COMPLIANT:
  
 END OF COMMENTS:
  