2007-12-07 10:04:53PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 10-31-07. COOLING LOAD
 CALCULATIONS FOR HP-1 ARE CALLING FOR 34,625 TOTAL
 BTU'S. MECHANICAL PLAN PAGE M2 HP-1 IS SHOWING 42,000
 TOTAL BTU'S. THE PLANS CAN NOT CALL FOR MORE THAN THE
 COOLING LOAD CAL'S., SEE 2004 FBC 13-407.1.ABC.1.1.
 PLEASE CORRECT. ( RESPONSE RECEIVED WAS ADDRESSING THE
 SENSIBLE COOLING BTU'S. AT 37,800). THE BUILDING CODE
 REQUIREMENT ADDRESS TOTAL BTU'S. NOT SENSIBLE BTU'S.
 PLEASE CORRECT.
  
 2) AS NOTED IN LAST REVIEW 10-31-07. COOLING LOAD
 CALCULATIONS FOR HP-2 ARE CALLING FOR 33,016 TOTAL
 BTU'S. MECHANICAL PLAN PAGE M2 HP-2 IS SHOWING 42,000
 TOTAL BTU'S. THE PLANS CAN NOT CALL FOR MORE THAN THE
 COOLING LOAD CAL'S., SEE 2004 FBC 13-407.1.ABC.1.1.
 PLEASE CORRECT. (SEE NOTE 1 RESPONSE).
  
 *** 2004 FBC 13-407.1.ABC.1.1 HVAC SYSTEMS AND
 EQUIPMENT SHALL BE SIZED TO PROVIDE NO MORE THAN THE
 SPACE AND SYSTEM LOADS CALCULATED IN ACCORDANCE WITH
 SECTION 407.1.ABC.1 . A SINGLE PIECE OF EQUIPMENT
 PROVIDING BOTH COOLING AND HEATING SHALL SATISFY THIS
 PROVISION WHEN THE COOLING FUNCTION MEETS THE
 PROVISIONS OF SECTION 407.1.ABC.1 , AND THE HEATING
 FUNCTION IS SIZED AS SMALL AS POSSIBLE TO MEET THE LOAD
 WITHIN AVAILABLE EQUIPMENT OPTIONS.
  
 3) ONLY ONE SET OF SUBMITTED PLANS HAD MECHANICAL PLANS
 PAGE M1 AND M2 IN THEM, AND THEY WERE NOT SIGNED AND
 SEALED BY THE ENGINEER, SEE 61G15-23.002. PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]