2007-12-07 10:04:53 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST |
| PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| (F.S.). |
| |
| *** DENIED *** |
| 1) AS NOTED IN LAST REVIEW 10-31-07. COOLING LOAD |
| CALCULATIONS FOR HP-1 ARE CALLING FOR 34,625 TOTAL |
| BTU'S. MECHANICAL PLAN PAGE M2 HP-1 IS SHOWING 42,000 |
| TOTAL BTU'S. THE PLANS CAN NOT CALL FOR MORE THAN THE |
| COOLING LOAD CAL'S., SEE 2004 FBC 13-407.1.ABC.1.1. |
| PLEASE CORRECT. ( RESPONSE RECEIVED WAS ADDRESSING THE |
| SENSIBLE COOLING BTU'S. AT 37,800). THE BUILDING CODE |
| REQUIREMENT ADDRESS TOTAL BTU'S. NOT SENSIBLE BTU'S. |
| PLEASE CORRECT. |
| |
| 2) AS NOTED IN LAST REVIEW 10-31-07. COOLING LOAD |
| CALCULATIONS FOR HP-2 ARE CALLING FOR 33,016 TOTAL |
| BTU'S. MECHANICAL PLAN PAGE M2 HP-2 IS SHOWING 42,000 |
| TOTAL BTU'S. THE PLANS CAN NOT CALL FOR MORE THAN THE |
| COOLING LOAD CAL'S., SEE 2004 FBC 13-407.1.ABC.1.1. |
| PLEASE CORRECT. (SEE NOTE 1 RESPONSE). |
| |
| *** 2004 FBC 13-407.1.ABC.1.1 HVAC SYSTEMS AND |
| EQUIPMENT SHALL BE SIZED TO PROVIDE NO MORE THAN THE |
| SPACE AND SYSTEM LOADS CALCULATED IN ACCORDANCE WITH |
| SECTION 407.1.ABC.1 . A SINGLE PIECE OF EQUIPMENT |
| PROVIDING BOTH COOLING AND HEATING SHALL SATISFY THIS |
| PROVISION WHEN THE COOLING FUNCTION MEETS THE |
| PROVISIONS OF SECTION 407.1.ABC.1 , AND THE HEATING |
| FUNCTION IS SIZED AS SMALL AS POSSIBLE TO MEET THE LOAD |
| WITHIN AVAILABLE EQUIPMENT OPTIONS. |
| |
| 3) ONLY ONE SET OF SUBMITTED PLANS HAD MECHANICAL PLANS |
| PAGE M1 AND M2 IN THEM, AND THEY WERE NOT SIGNED AND |
| SEALED BY THE ENGINEER, SEE 61G15-23.002. PLEASE |
| CORRECT. |
| |