2007-12-06 11:47:53 | ** DENIED 2ND REVIEW ** |
| |
| ** PLEASE SEE COMMENTS FROM PREVIOUS REVIEW AS THERE IS |
| NEED FOR SOME CORRECTIONS/ADJUSTMENTS. |
| |
| |
| 1) NOTE: PLEASE SEE THE PARTIALLY COMPLETED METHOD *C* |
| SHEETS SUBMITTED. ONLY ONE OF THE SHEETS WERE SIGNED |
| DATED AND SEAL. |
| AS THE SPACE IS HAS EXISTING AIR CONDITIONING, THE |
| ELECTRICAL REVIEW ONLY NEEDS LIGHTING PERFORMANCE |
| CALCULATIONS. PLEASE SEE PART OF A CALCULATIONS SHEET |
| MENTIONS A SERVER ROOM WITH A ALLOWANCE/DESIGN OF 2.0. |
| PLEASE PROVIDE WHERE AN ALLOWANCE OF 2.0 COMES FROM. |
| PLEASE ALSO SEE BASED ON THE FIXTURES ON PLANS AND SQ |
| FT, THIS DOES NOT SEEM TO BE POSSIBLE? |
| PLEASE KNOW IF USING SPACE BY SPACE, 13-415.2.B, OR |
| 13-415.2.C.1, THIS CAN BE DONE ON A TABLE OF SOME SORT. |
| PLEASE CALL TO GO OVER. |
| |
| 2) NOTE: PLEASE SHOW THE LOCATIONS OF NEW PANELS AND |
| SERVICE EQUIPMENT WHICH IS BEING NOTED TO BE INSTALLED |
| IN SPACE. |
| 110.26, 408.17, 240.24 ETC FOR REVIEW. |
| FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| |
| 3) NOTE: PLEASE SEE BOTH SETS OF PLANS ARE NOT |
| COMPLETE. ONLY ONE SET CONTAINS ELECTRICAL SHEET. A E-2 |
| AND A E-3. |
| PLEASE SUBMIT TWO COMPLETE SETS FOR REVIEW. |
| 106.1 |
| |
| ** PLEASE KNOW THAT A FIELD INSPECTION MAY BE NEEDED TO |
| GO OVER EXISTING WORK AND PROPOSED NEW. |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |