2007-10-31 11:04:39PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) COOLING LOAD CALCULATIONS FOR HP-1 ARE CALLING FOR
 34,625 TOTAL BTU'S. MECHANICAL PLAN PAGE M2 HP-1 IS
 SHOWING 42,000 TOTAL BTU'S. THE PLANS CAN NOT CALL FOR
 MORE THAN THE COOLING LOAD CAL'S., SEE 2004 FBC
 13-407.1.ABC.1.1. PLEASE CORRECT.
  
 2) COOLING LOAD CALCULATIONS FOR HP-2 ARE CALLING FOR
 33,016 TOTAL BTU'S. MECHANICAL PLAN PAGE M2 HP-2 IS
 SHOWING 42,000 TOTAL BTU'S. THE PLANS CAN NOT CALL FOR
 MORE THAN THE COOLING LOAD CAL'S., SEE 2004 FBC
 13-407.1.ABC.1.1. PLEASE CORRECT.
  
 *** 2004 FBC 13-407.1.ABC.1.1 HVAC SYSTEMS AND
 EQUIPMENT SHALL BE SIZED TO PROVIDE NO MORE THAN THE
 SPACE AND SYSTEM LOADS CALCULATED IN ACCORDANCE WITH
 SECTION 407.1.ABC.1 . A SINGLE PIECE OF EQUIPMENT
 PROVIDING BOTH COOLING AND HEATING SHALL SATISFY THIS
 PROVISION WHEN THE COOLING FUNCTION MEETS THE
 PROVISIONS OF SECTION 407.1.ABC.1 , AND THE HEATING
 FUNCTION IS SIZED AS SMALL AS POSSIBLE TO MEET THE LOAD
 WITHIN AVAILABLE EQUIPMENT OPTIONS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]