Plan Review Notes
Plan Review Notes For Permit 07100587
Permit Number 07100587
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-29 09:45:11 
  
 *** DENIED ***
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
  
 THIS IS REQUIRED FOR BOTH THE ARCHITECTURAL TITLE
 SHEETS AND ELECTRICAL PLANS.
  
 2) NOTE: PLEASE SEE THE METHOD *A* ENERGY CALCULATIONS
 SUBMITTED MAY NOT BE USED. METHOD *A* IS FOR WHOLE
 BUILDING METHOD.
 PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS PER
 13-415.2.
 PLEASE COMPLETE THE FIXTURE LEGEND AND CORRELATE WITH
 THE LPC WHICH ARE TO BE SUBMITTED.
  
 3) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR FIRE
 ALARMS DEVICES PER FBC 11-4.28.1,.2 AND .3(4).
  
 4) NOTE: PLEASE SEE 408.4, FBC 106.1, 106.3.5.1.2,
 106.3. PLEASE SEE THE CIRCUITS NEED TO BE SPECIFIC TO
 THE ROOMS AND AREAS IN WHICH THEY FEED.
 PLEASE SEE THE USE OF RECEPTACLES NEEDS TO BE MORE
 SPECIFIC TO ROOM DESIGNATIONS. THIS CAN BE DONE BY
 ALPHA OR NUMERIC DESIGNATIONS.
  
 5) NOTE: PLEASE DO NOT ATTACH ANY SUPPORTING DOCUMENTS
 DOWN THE LEFT HAND SIDE OF PLANS. ** THIS IS NOTED AS
 THE DOCUMENTS WHICH WERE ATTACHED HAVE BEEN REMOVED.
  
  
 ** PLEASE KNOW AS SOME INFORMATION HAS NOT YET BEEN
 SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW
 COMMENTS ON THE NEXT REVIEW.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  