Plan Review Notes
Plan Review Notes For Permit 07100567
Permit Number 07100567
Review Stop B
Sequence Number 1
Notes
Date Text
2007-10-23 18:16:18****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN
 PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE
 DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY A
 DESIGN PROFESSIONAL. DOCUMENTS PREPARED BY AN ARCHITECT
 OR ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED SEALED ORIGINALS FAC61G15, FAC61G1 16.
  
 2. SEE FBC1003.6, MEANS OF EGRESS CONTINUITY.THE PATH
 OF EGRESS TRAVEL ALONG A MEANS OF EGRESS SHALL NOT BE
 INTERRUPTED BY ANY BUILDING ELEMENT OTHER THAN A MEANS
 OF EGRESS COMPONENT AS SPECIFIED IN CHAPTER 10.
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL REQUIRED EXITS
 AND LOCATIN OF ALL EXIT LIGHTS.