Plan Review Notes For Permit 07100564 |
Permit Number |
07100564 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-12-14 11:38:26 | 2004 FBC W/2007 REVISIONS | | LEVEL 2 ALTERATIONS | | | | 1) A RECORDED COPY OF THE NOTICE OF | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | PERMIT CAN BE ISSUED. | | | | 2) ON SHEET SP-1 THE OCCUPANCY TYPE IS INCORRECTLY | | SPECIFIED AS R-2. IT SHOULD BE R-3 FOR A SINGLE FAMILY | | DWELLING. FBC CHAPTER 3. | | | | 3) ALSO ON SP-1 THE CODE SHOULD BE THE 2004 FBC WITH | | 2007 REVISIONS. | | | | 4) SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR THE | | EXTERIOR DOORS IN THE SCHEDULE ON SHEET S-3. SEE FBC R | | 301.2(2). | | | | 5) SUBMIT PRODUCT APPROVALS FOR THE DOUBLE OUTSWING | | GLAZED DOORS WITH SIDELITES (OXXO). SEE FAC RULE9B-72. | | | | 6) SUBMIT PRODUCT APPROVALS FOR THE SINGLE OUTSWING | | GLAZED DOOR WITH SIDELITES (X) SEE FAC RULE 9B-72. | | | | 7) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE | | JELD-WEN AWNINGAND CASEMENT WINDOWS DO NOT INDICATE | | IF THEY ARE IMPACT RESISTANT. SUBMIT THIS INFORMATION | | OR PROVIDE IMPACT PROTECTION AS REQUIRED BY FBC R | | 301.2.1.2. | | | | 8) SUBMIT A KEY PLAN AND INSTALLATION SCHEDULE FOR THE | | EASTERN METAL SUPPLY STORM PANEL PRODUCT APPROVALS THAT | | WERE SUBMITTED. SPECIFY WHICH OPENINGS WILL BE | | SHUTTERED. SPECIFY THE MOUNT TYPE, ANCHOR TYPE, ANCHOR | | SPACING, ETC. SEE ATTACHED INSTALLATION SCHEDULE. FBC | | 106.1.2* CITY AMENDMENTS | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] | | |
|