Plan Review Notes
Plan Review Notes For Permit 07100564
Permit Number 07100564
Review Stop B
Sequence Number 2
Notes
Date Text
2007-12-14 11:38:262004 FBC W/2007 REVISIONS
 LEVEL 2 ALTERATIONS
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) ON SHEET SP-1 THE OCCUPANCY TYPE IS INCORRECTLY
 SPECIFIED AS R-2. IT SHOULD BE R-3 FOR A SINGLE FAMILY
 DWELLING. FBC CHAPTER 3.
  
 3) ALSO ON SP-1 THE CODE SHOULD BE THE 2004 FBC WITH
 2007 REVISIONS.
  
 4) SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR THE
 EXTERIOR DOORS IN THE SCHEDULE ON SHEET S-3. SEE FBC R
 301.2(2).
  
 5) SUBMIT PRODUCT APPROVALS FOR THE DOUBLE OUTSWING
 GLAZED DOORS WITH SIDELITES (OXXO). SEE FAC RULE9B-72.
  
 6) SUBMIT PRODUCT APPROVALS FOR THE SINGLE OUTSWING
 GLAZED DOOR WITH SIDELITES (X) SEE FAC RULE 9B-72.
  
 7) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 JELD-WEN AWNINGAND CASEMENT WINDOWS DO NOT INDICATE
 IF THEY ARE IMPACT RESISTANT. SUBMIT THIS INFORMATION
 OR PROVIDE IMPACT PROTECTION AS REQUIRED BY FBC R
 301.2.1.2.
  
 8) SUBMIT A KEY PLAN AND INSTALLATION SCHEDULE FOR THE
 EASTERN METAL SUPPLY STORM PANEL PRODUCT APPROVALS THAT
 WERE SUBMITTED. SPECIFY WHICH OPENINGS WILL BE
 SHUTTERED. SPECIFY THE MOUNT TYPE, ANCHOR TYPE, ANCHOR
 SPACING, ETC. SEE ATTACHED INSTALLATION SCHEDULE. FBC
 106.1.2* CITY AMENDMENTS
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  