2007-11-05 14:00:36 | 2004 FBC W/2007 REVISIONS |
| LEVEL 2 ALTERATIONS |
| |
| DENIED BY BUILDING |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) THE PRINTED NAME AND SIGNATURE OF THE PERSON |
| RESPONSIBLE FOR THE DESIGN IS REQUIRED ON EACH DRAWING. |
| FBC * 106.1.2 QUALITY OF PLANS |
| BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH |
| SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE |
| MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND |
| SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| OTHER ITEMS RELATED TO RECORDS MANAGEMENT. |
| |
| 3) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| LAWS, SEE F.B.C. 106.1.1 CITY AMENDMENTS. |
| |
| 4) PROVIDE DIMENSIONS ON THE PLANS FOR THE NEW WALLS, |
| OPENINGS, ROOMS, WINDOWS, DOORS, ETC.SPECIFY THE |
| WINDOW TYPES AND SIZES ON THE DRAWINGS. FBC 106.1.1 |
| CITY AMENDMENTS. |
| |
| 5) PROVIDE WALL SECTIONS FOR INTERIOR WALLS. INDICATE |
| THE MATERIAL, SIZE AND SPACING OF FRAMING.F.B.C. |
| 106.1.1 CITY AMENDMENTS. |
| |
| 6) THE EXTERIOR WALL FRAMING DETAIL FOR THE NEW WINDOWS |
| AND DOORS DOES NOT CONTAIN ENOUGH INFORMATION. SPECIFY |
| THE FRAMING MATERIAL, SPACING, HEADER SIZES, OPENING |
| SIZES, NUMBER OF JACKS, INSULATION, INTERIOR AND |
| EXTERIOR WALL COVERINGS, SHOW ADEQUATE SUBSTRATE FOR |
| ATTACHING STORM PANELS, SPECIFY THE CONNECTORS THAT |
| WILL BE USED. BE SPECIFIC. FBC 106.1.1 CITY |
| AMENDMENTS. |
| |
| 7)FBC 1606.1.4SHUTTERS. |
| INSTALLATION/DESIGN INFORMATION |
| REQUIRED.SUBMIT AN INSTALLATION |
| SCHEDULE INCLUDING THE FOLLOWING |
| DETAILS: |
| (A) BUILDING CONSTRUCTION TYPE (EG CBS) |
| (B) BUILDING (OR INSTALLATION) HEIGHT |
| (C) DESIGN PRESSURE FOR EACH OPENING |
| (D) OPENING SIZES |
| (E) SHUTTER SPAN (VERTICAL/HORIZONTAL?) |
| (F) ANCHOR TYPE, SIZE AND SPACING |
| A FORM IS AVAILABLE FROM THIS OFFICE |
| GIVING THE RECOMMENDED INSTALLATION |
| SCHEDULE FORMAT.SUBMIT THE ABOVE |
| INFORMATION WHICH IS REQUIRED FOR |
| REVIEW. |
| |
| 8) THE PRODUCT APPROVAL SUBMITTED FOR THE FRENCH DOOR |
| IS FOR A SINGLE OUTSWING DOOR WITH SIDELITES (OXO). THE |
| DRAWINGS INDICATE A DOUBLE OUTSWING DOOR WITH NO |
| SIDELITES INDICATED. PLEASE CLARIFY. |
| |
| 9) THE PRODUCT APPROVAL SUBMITTED FOR THE STORM PANELS |
| IS INCOMPLETE. THE INSTALLATION DRAWINGS 05-078 SHEETS |
| 1-15 ARE MISSING. SEE RULE FAC 9B-72. |
| |
| 10) THE PRODUCT APPROVALS SUBMITTED FOR THE JELD-WEN |
| CASEMENT AND AWNING WINDOWS DO NOT SPECIFY THE DESIGN |
| PRESSURES. THE DESIGN PRESSURES ARE REQUIRED TO |
| DETERMINE IF THE WINDOWS MEET THE COMPONENT AND |
| CLADDING PRESSURES FOR THE STRUCTURE. SEE FBC TABLE |
| R301.2(2). |
| |
| 11)106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE |
| PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |