Plan Review Notes
Plan Review Notes For Permit 07100564
Permit Number 07100564
Review Stop B
Sequence Number 1
Notes
Date Text
2007-11-05 14:00:362004 FBC W/2007 REVISIONS
 LEVEL 2 ALTERATIONS
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN IS REQUIRED ON EACH DRAWING.
 FBC * 106.1.2 QUALITY OF PLANS
 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
  
 3) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, SEE F.B.C. 106.1.1 CITY AMENDMENTS.
  
 4) PROVIDE DIMENSIONS ON THE PLANS FOR THE NEW WALLS,
 OPENINGS, ROOMS, WINDOWS, DOORS, ETC.SPECIFY THE
 WINDOW TYPES AND SIZES ON THE DRAWINGS. FBC 106.1.1
 CITY AMENDMENTS.
  
 5) PROVIDE WALL SECTIONS FOR INTERIOR WALLS. INDICATE
 THE MATERIAL, SIZE AND SPACING OF FRAMING.F.B.C.
 106.1.1 CITY AMENDMENTS.
  
 6) THE EXTERIOR WALL FRAMING DETAIL FOR THE NEW WINDOWS
 AND DOORS DOES NOT CONTAIN ENOUGH INFORMATION. SPECIFY
 THE FRAMING MATERIAL, SPACING, HEADER SIZES, OPENING
 SIZES, NUMBER OF JACKS, INSULATION, INTERIOR AND
 EXTERIOR WALL COVERINGS, SHOW ADEQUATE SUBSTRATE FOR
 ATTACHING STORM PANELS, SPECIFY THE CONNECTORS THAT
 WILL BE USED. BE SPECIFIC. FBC 106.1.1 CITY
 AMENDMENTS.
  
 7)FBC 1606.1.4SHUTTERS.
 INSTALLATION/DESIGN INFORMATION
 REQUIRED.SUBMIT AN INSTALLATION
 SCHEDULE INCLUDING THE FOLLOWING
 DETAILS:
 (A) BUILDING CONSTRUCTION TYPE (EG CBS)
 (B) BUILDING (OR INSTALLATION) HEIGHT
 (C) DESIGN PRESSURE FOR EACH OPENING
 (D) OPENING SIZES
 (E) SHUTTER SPAN (VERTICAL/HORIZONTAL?)
 (F) ANCHOR TYPE, SIZE AND SPACING
 A FORM IS AVAILABLE FROM THIS OFFICE
 GIVING THE RECOMMENDED INSTALLATION
 SCHEDULE FORMAT.SUBMIT THE ABOVE
 INFORMATION WHICH IS REQUIRED FOR
 REVIEW.
  
 8) THE PRODUCT APPROVAL SUBMITTED FOR THE FRENCH DOOR
 IS FOR A SINGLE OUTSWING DOOR WITH SIDELITES (OXO). THE
 DRAWINGS INDICATE A DOUBLE OUTSWING DOOR WITH NO
 SIDELITES INDICATED. PLEASE CLARIFY.
  
 9) THE PRODUCT APPROVAL SUBMITTED FOR THE STORM PANELS
 IS INCOMPLETE. THE INSTALLATION DRAWINGS 05-078 SHEETS
 1-15 ARE MISSING. SEE RULE FAC 9B-72.
  
 10) THE PRODUCT APPROVALS SUBMITTED FOR THE JELD-WEN
 CASEMENT AND AWNING WINDOWS DO NOT SPECIFY THE DESIGN
 PRESSURES. THE DESIGN PRESSURES ARE REQUIRED TO
 DETERMINE IF THE WINDOWS MEET THE COMPONENT AND
 CLADDING PRESSURES FOR THE STRUCTURE. SEE FBC TABLE
 R301.2(2).
  
 11)106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]