2007-10-18 14:55:03****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
  
 1.)EFFECTIVE OCTOBER 1, 2007, SECONDARY WATER BARRIER
 REQUIRED FS553.844(5)(A). PROVIDE INFORMATION
 (PRODUCT APPROVAL OR SPECIFICATIONS) TO SHOW HOW YOU
 WILL COMPLY WITH THIS REQUIREMENT.
  
 2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING INFORMATION
 ON THE APPLICATION, SEE ATTACHED POLICY; MEAN ROOF
 HEIGHT, ROOF PITCH, ROOF DECK TYPE, AREA OF EACH ROOF
 TYPE
  
 3.) PROPERTY APPRAISER RECORDS SHOW THAT THIS BUILDING
 IS 1096 SF.EITHER REVISE THE APPLICATON OR PROVIDE A
 ROOF PLAN TO SHOW HOW THE REROOF AREA IS 850SF.
  