Plan Review Notes For Permit 07100523 |
Permit Number |
07100523 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-10-26 11:21:18 | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS, | | CONDUIT AND CONDUCTOR SIZE AND TYPE, AND OCP FOR THE | | EQUIPMENT BEING WIRED UNDER THIS PERMIT. 106.3.5.1.2 | | FBC AS AMENDED. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|