Plan Review Notes
Plan Review Notes For Permit 07100508
Permit Number 07100508
Review Stop B
Sequence Number 4
Notes
Date Text
2009-09-09 13:37:12BUILDING REVISIONS
  
 1) THE LETTER SUBMITTED TO CHANGE FROM ICYNENE SPRAY
 FOAM INSULATION WITH UNVENTED ATTIC IS DENIED. SUBMIT
 TWO SETS OF SIGNED AND SEALED REVISED DRAWINGS SHOWING
 THE R-30 BATT INSULATION IN THE CEILINGS AND THE ATTIC
 VENTILATION REQUIRED BY FBC R806. REVISED ENERGY
 CALCULATIONS ARE REQUIRED.
  
 2) THE CEILING FRAMING DETAIL AND 2X4 WOOD DOOR BUCK
 DETAIL ARE OK.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714