2007-11-02 09:20:39DENIED;
 1. PAGE P-1 MASTER SHOWER DRAIN IS MORE THAN 6' FROM
 TRAP TO VENTED LINE. SEE FBC- PLUMBING TABLE 906.1.
 2. SANITARY RISER DIAGRAM MASTER BATH. PIPE SIZE AFTER
 SHOWER MUST GO FROM 2" TO 3" SEE WET VENT TABLE 909.3.
 3. PORCH DRAINS ARE STORM WATER DRAIN NO TRAP OR TRAP
 PRIMER ARE REQUIRED PLEASE CORRECT.
 4. SHOW SECONDARY ROOF DRAINS OR SCUPPERS ON PLANS SEE
 CHAPTER 11 .
 5. SHOW SIZE OF GAS WATER HEATER AND HOW IT WILL BE
 VENTED WITH REQUIRED CLEARANCES FROM BURNABLES