2007-10-22 14:51:00 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST |
| PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| (F.S.). |
| |
| *** DENIED *** |
| 1) PLEASE STATE ON PLAN M-1 WHICH EXHAUST FAN IS TO BE |
| INSTALLED IN THE FIRST FLOOR BATHROOM (EF-1 OR EF-2). |
| SEE FBC/R R303.3 EXCEPT.. |
| |
| 2) PLEASE SHOW ON PAGE M-1 THE SIZE OF THE RETURN AIR |
| TRANSFER DUCT TO BEDROOM 2. SEE FBC/R M1602.4. |
| |
| 3) PLEASE SHOW THE COMBUSTION AIR CALCULATIONS FOR THE |
| GAS CLOTHES DRYER AND PROVIDE COMBUSTION AIR. SEE FBC/R |
| G2407.1 |
| |
| 4) PLEASE PROVIDE FOR MAKEUP AIR FOR THE GAS CLOTHES |
| DRYER. SEE FBC/R G2407.4. |
| |
| 5) PLEASE SUBMIT DETAILED MANUFACTURER'S |
| SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR THE |
| PREFABRICATED GAS FIREPLACE AND ALSO THE GAS GRILL IN |
| THE COVERED PORCH. SEE FBC 106.1 |
| *** BE ADVISED THE GAS GRILL IN THE COVERED PORCH MAY |
| REQUIRE AN APPROVED HOOD. SEE FBC/R M1504.1. |
| |
| 6) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT |
| ALSO, SEE 2004 FBC 13-600.3.ABC.2. |
| |