2007-10-22 14:51:00PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE STATE ON PLAN M-1 WHICH EXHAUST FAN IS TO BE
 INSTALLED IN THE FIRST FLOOR BATHROOM (EF-1 OR EF-2).
 SEE FBC/R R303.3 EXCEPT..
  
 2) PLEASE SHOW ON PAGE M-1 THE SIZE OF THE RETURN AIR
 TRANSFER DUCT TO BEDROOM 2. SEE FBC/R M1602.4.
  
 3) PLEASE SHOW THE COMBUSTION AIR CALCULATIONS FOR THE
 GAS CLOTHES DRYER AND PROVIDE COMBUSTION AIR. SEE FBC/R
 G2407.1
  
 4) PLEASE PROVIDE FOR MAKEUP AIR FOR THE GAS CLOTHES
 DRYER. SEE FBC/R G2407.4.
  
 5) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR THE
 PREFABRICATED GAS FIREPLACE AND ALSO THE GAS GRILL IN
 THE COVERED PORCH. SEE FBC 106.1
 *** BE ADVISED THE GAS GRILL IN THE COVERED PORCH MAY
 REQUIRE AN APPROVED HOOD. SEE FBC/R M1504.1.
  
 6) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, SEE 2004 FBC 13-600.3.ABC.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]