Date |
Text |
2007-10-20 11:26:40 | ** DENIED ** |
| |
| |
| 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| UNDER THE NEW CODES ADOPTED BY THE STATE. |
| PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| AFFECT DESIGNS FOR ALL TRADES. |
| PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| REVIEWER AT A MINIMUM. |
| 2005 NFPA-70 (SHOWN) |
| 2002 NFPA-72 |
| |
| 2) NOTE: PLEASE SEE NFPA-72 FOR DEFINITIONS OF SMOKE |
| DETECTORS. THE PLANS CALL FOR SD ALONG WITH NOTES AND |
| LEGEND WHICH STAND FOR SMOKE DETECTORS. PLEASE SEE BY |
| DEFINITION OF A SD THIS IS A DEVICE WHICH ONLY DETECTS |
| AND WOULD SIGNAL OTHER DEVICES FOR ALARM AND SOUNDING. |
| PLEASE SEE HOWEVER THESE ARE BEING SHOWN CIRCUITED AS |
| 120V UNITS. |
| PLEASE LOCATIONS OF SOUNDING DEVICES AND FIRE ALARM |
| SYSTEM IF INDEED THESE ARE SMOKE DETECTORS. |
| ** IF THESE ARE ACTUALLY 120VA UNITS WHICH DETECT AND |
| SOUND AN ALARM, THEN THESE BY DEFINITIONS IN NFPA-72 |
| WOULD BE SA FOR SMOKE ALARMS. YOU CAN SEE IN THE FBC |
| AND RESIDENTIAL CODES ALONG WITH NFPA THESE ARE |
| INDICATED AS *ALARMS*. |
| ** PLEASE ALSO SEE NOTE ON E-2 MENTIONS THE SMOKE |
| DETECTORS ARE TO BE WIRED TO THE BATH OR KITCHEN |
| LIGHTING CIRCUIT(S), HOWEVER AS SHOWN ON PLANS THESE |
| ARE BEING WIRED TO THE BEDROOM LIGHTING CIRCUIT. |
| |
| IT IS NOT KNOWN TO THE OFFICE WHICH ACTUAL SYSTEM IS |
| BEING INSTALLED HOWEVER SEEMS THIS ACTUALLY NEED TO BE |
| ADJUSTED TO SHOW SA/SMOKE ALARMS. PLEASE ADJUST ANY |
| NOTES, LEGEND ETC AS NEEDED. |
| |
| 3) NOTE: PLEASE SEE THE LOAD CALCULATIONS ARE CALLING |
| FOR 13 SMALL APPLIANCE CIRCUITS WHICH DOES NOT |
| CORRELATE WITH THE PANEL SCHEDULE(S). THE OTHER |
| APPLIANCES SUCH AS THE DISHWASHER, MICROWAVE ETC IS NOT |
| TYPICALLY CALLED SMALL APPLIANCE CIRCUITS AND IS NOT |
| SHOWN AS THIS ON PLANS OR PANEL SCHEDULES. THESE ARE |
| DEDICATED CIRCUITS WHICH WOULD BE LISTED IN LOAD |
| CALCULATIONS ACCORDINGLY.IT IS NOTED THAT THE SAME |
| 1500VA IS BEING USED WHICH IS OK. |
| PLEASE SEE 210.52B1 AS AREAS WHICH ARE BREAKFAST AREAS |
| AND THE LIKE ARE ALSO REQUIRED TO BE ON ONE *OR MORE* |
| OF THE SMALL APPLIANCE CIRCUITS. |
| PLEASE SEE BREAKFAST EATING AREA ALONG WITH BAR AREA |
| WHICH IS CIRCUIT #22. |
| 210.11C1, 220.52 |
| |
| 4) NOTE: PLEASE VERIFY 210.4B FOR DISHWASHERS AND |
| DISPOSALS. IF THESE UNITS ARE GOING TO BE FED FROM A |
| DEVICE WITH THE SAME YOKE, THEN THE BREAKER FEEDING |
| THIS SINGLE DEVICE/YOKE WOULD BE NEED TO BE A 2-POLE |
| BREAKER. |
| THIS IS ONLY NOTED FOR VERIFICATION AS PLANS DO SHOW |
| TWO INDIVIDUAL SINGLE RECEPTACLES. **NO CHANGE IS |
| NEEDED AND ONLY NOTED** |
| |
| 5) NOTE: PLEASE SEE210.70 AND LS 101 7.8 AS AT LEAST |
| ONE ELECTRICAL LIGHT FIXTURE IS REQUIRED OUTSIDE THE |
| FRONT EGRESS FOR ILLUMINATION. THESE ARE ALL CURRENTLY |
| SHOWN AS J-BOXES. |
| |
| 6) NOTE: PLEASE SEE MISSING FOOTER STEEL AS PART OF THE |
| GROUNDING ELECTRODE SYSTEM. 250.50 |
| |
| 7) NOTE: PLEASE SEE RECEPTACLE ON THE STAIR SIDE OF |
| DINING ROOM NEEDS TO BE WITHIN 6FT OF THE EDGE OF THE |
| WALL. THIS COULD BE REDLINED, HOWEVER PLEASE CORRECT AT |
| TIME AS PLANS ARE IN NEED OF SOME OTHER ADJUSTMENTS. |
| |
| 8) NOTE: PLEASE SEE 210.8A7 AS ALL 15/20AMP RECEPTACLES |
| WITHIN 6FT OF LAUNDRY SINKS ARE ALSO REQUIRED TO HAVE |
| GFI PROTECTION. THIS INCLUDES SINGLE RECEPTACLES SUCH |
| AS THE WASHING MACHINE. THE PLANS APPEAR TO SHOW AS |
| SINK IN THIS ROOM. |
| THIS IS NEW IN THE 2005 NEC. |
| |
| 9) NOTE: PLANS WERE SUBMITTED WITH AN AFFIDAVIT WHICH |
| WAS DONE BY THE ARCHITECT AND A LICENSED PLAN REVIEWER |
| HOWEVER THIS WAS NOT SUBMITTED AS A *PRIVATE PROVIDER* |
| PROJECT PER FS 553.791. THIS WAS CONFIRMED ON THE FRONT |
| COUNTER UPON SUBMISSION OF PLANS. |
| |
| ** PLEASE KNOW MANY OF THE ABOVE ITEMS COULD BE |
| REDLINED HOWEVER PLANS ARE COMING BACK FOR |
| CORRECTIONS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |