Plan Review Notes
Plan Review Notes For Permit 07100508
Permit Number 07100508
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-20 11:26:40** DENIED **
  
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2005 NFPA-70 (SHOWN)
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE NFPA-72 FOR DEFINITIONS OF SMOKE
 DETECTORS. THE PLANS CALL FOR SD ALONG WITH NOTES AND
 LEGEND WHICH STAND FOR SMOKE DETECTORS. PLEASE SEE BY
 DEFINITION OF A SD THIS IS A DEVICE WHICH ONLY DETECTS
 AND WOULD SIGNAL OTHER DEVICES FOR ALARM AND SOUNDING.
 PLEASE SEE HOWEVER THESE ARE BEING SHOWN CIRCUITED AS
 120V UNITS.
 PLEASE LOCATIONS OF SOUNDING DEVICES AND FIRE ALARM
 SYSTEM IF INDEED THESE ARE SMOKE DETECTORS.
 ** IF THESE ARE ACTUALLY 120VA UNITS WHICH DETECT AND
 SOUND AN ALARM, THEN THESE BY DEFINITIONS IN NFPA-72
 WOULD BE SA FOR SMOKE ALARMS. YOU CAN SEE IN THE FBC
 AND RESIDENTIAL CODES ALONG WITH NFPA THESE ARE
 INDICATED AS *ALARMS*.
 ** PLEASE ALSO SEE NOTE ON E-2 MENTIONS THE SMOKE
 DETECTORS ARE TO BE WIRED TO THE BATH OR KITCHEN
 LIGHTING CIRCUIT(S), HOWEVER AS SHOWN ON PLANS THESE
 ARE BEING WIRED TO THE BEDROOM LIGHTING CIRCUIT.
  
 IT IS NOT KNOWN TO THE OFFICE WHICH ACTUAL SYSTEM IS
 BEING INSTALLED HOWEVER SEEMS THIS ACTUALLY NEED TO BE
 ADJUSTED TO SHOW SA/SMOKE ALARMS. PLEASE ADJUST ANY
 NOTES, LEGEND ETC AS NEEDED.
  
 3) NOTE: PLEASE SEE THE LOAD CALCULATIONS ARE CALLING
 FOR 13 SMALL APPLIANCE CIRCUITS WHICH DOES NOT
 CORRELATE WITH THE PANEL SCHEDULE(S). THE OTHER
 APPLIANCES SUCH AS THE DISHWASHER, MICROWAVE ETC IS NOT
 TYPICALLY CALLED SMALL APPLIANCE CIRCUITS AND IS NOT
 SHOWN AS THIS ON PLANS OR PANEL SCHEDULES. THESE ARE
 DEDICATED CIRCUITS WHICH WOULD BE LISTED IN LOAD
 CALCULATIONS ACCORDINGLY.IT IS NOTED THAT THE SAME
 1500VA IS BEING USED WHICH IS OK.
 PLEASE SEE 210.52B1 AS AREAS WHICH ARE BREAKFAST AREAS
 AND THE LIKE ARE ALSO REQUIRED TO BE ON ONE *OR MORE*
 OF THE SMALL APPLIANCE CIRCUITS.
 PLEASE SEE BREAKFAST EATING AREA ALONG WITH BAR AREA
 WHICH IS CIRCUIT #22.
 210.11C1, 220.52
  
 4) NOTE: PLEASE VERIFY 210.4B FOR DISHWASHERS AND
 DISPOSALS. IF THESE UNITS ARE GOING TO BE FED FROM A
 DEVICE WITH THE SAME YOKE, THEN THE BREAKER FEEDING
 THIS SINGLE DEVICE/YOKE WOULD BE NEED TO BE A 2-POLE
 BREAKER.
 THIS IS ONLY NOTED FOR VERIFICATION AS PLANS DO SHOW
 TWO INDIVIDUAL SINGLE RECEPTACLES. **NO CHANGE IS
 NEEDED AND ONLY NOTED**
  
 5) NOTE: PLEASE SEE210.70 AND LS 101 7.8 AS AT LEAST
 ONE ELECTRICAL LIGHT FIXTURE IS REQUIRED OUTSIDE THE
 FRONT EGRESS FOR ILLUMINATION. THESE ARE ALL CURRENTLY
 SHOWN AS J-BOXES.
  
 6) NOTE: PLEASE SEE MISSING FOOTER STEEL AS PART OF THE
 GROUNDING ELECTRODE SYSTEM. 250.50
  
 7) NOTE: PLEASE SEE RECEPTACLE ON THE STAIR SIDE OF
 DINING ROOM NEEDS TO BE WITHIN 6FT OF THE EDGE OF THE
 WALL. THIS COULD BE REDLINED, HOWEVER PLEASE CORRECT AT
 TIME AS PLANS ARE IN NEED OF SOME OTHER ADJUSTMENTS.
  
 8) NOTE: PLEASE SEE 210.8A7 AS ALL 15/20AMP RECEPTACLES
 WITHIN 6FT OF LAUNDRY SINKS ARE ALSO REQUIRED TO HAVE
 GFI PROTECTION. THIS INCLUDES SINGLE RECEPTACLES SUCH
 AS THE WASHING MACHINE. THE PLANS APPEAR TO SHOW AS
 SINK IN THIS ROOM.
 THIS IS NEW IN THE 2005 NEC.
  
 9) NOTE: PLANS WERE SUBMITTED WITH AN AFFIDAVIT WHICH
 WAS DONE BY THE ARCHITECT AND A LICENSED PLAN REVIEWER
 HOWEVER THIS WAS NOT SUBMITTED AS A *PRIVATE PROVIDER*
 PROJECT PER FS 553.791. THIS WAS CONFIRMED ON THE FRONT
 COUNTER UPON SUBMISSION OF PLANS.
  
 ** PLEASE KNOW MANY OF THE ABOVE ITEMS COULD BE
 REDLINED HOWEVER PLANS ARE COMING BACK FOR
 CORRECTIONS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]