2007-12-10 16:16:082004 FBC W/2007 REVISIONS
  
 DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) SHOW COMPLIANCE WITH R302.1 EXTERIOR WALLS. EXTERIOR
 WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM) SHALL
 HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE RATING
 WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL NOT
 EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM AN
 ADJACENT PROJECTION OR WALL. ONE WALL OF THE STRUCTURE
 IS LESS THAN 6 FEET FROM THE PROPERTY LINE.
  
 3) THE PLANS ARE MISSING SHEET A-5.2. WHICH IS LISTED
 IN THE DRAWING INDEX ON A-0.
  
 4) SUBMIT FIREPLACE AND CHIMNEY DETAILS. SHOW
 COMPLIANCE WITH R1003 FOR MASONRY FIREPLACES OR R1004
 FOR FACTORY BUILT FIREPLACES AND R1001 FOR MASONRY
 CHIMNEYS OR R1002 FOR FACTORY BUILT CHIMNEYS. IF USING
 FACTORY BUILT APPLIANCES SUBMIT MANUFACTURER'S
 SPECIFICATIONS AND LISTING INFORMATION.
  
 5) PROVIDE A WINDOW SCHEDULE ON THE PLANS. IDENTIFY THE
 TYPES OF WINDOWS AND THEIR LOCATIONS. FBC 106.1.1* CITY
 AMENDMENTS.
  
 6) SHOW COMPLIANCE WITH R502.1.2 DRAFTSTOPPING
 REQUIRED.
 WHEN THERE IS USABLE SPACE BOTH ABOVE AND BELOW THE
 CONCEALED SPACE OF A FLOOR/CEILING ASSEMBLY, DRAFTSTOPS
 SHALL BE INSTALLED SO THAT THE AREA OF THE CONCEALED
 SPACE DOES NOT EXCEED 1,000 SQUARE FEET (92.9 M 2 ).
 DRAFTSTOPPING SHALL DIVIDE THE CONCEALED SPACE INTO
 APPROXIMATELY EQUAL AREAS. WHERE THE ASSEMBLY IS
 ENCLOSED BY A FLOOR MEMBRANE ABOVE AND A CEILING
 MEMBRANE BELOW DRAFTSTOPPING SHALL BE PROVIDED IN
 FLOOR/CEILING ASSEMBLIES UNDER THE FOLLOWING
 CIRCUMSTANCES:
 1. CEILING IS SUSPENDED UNDER THE FLOOR FRAMING.2.
 FLOOR FRAMING IS CONSTRUCTED OF TRUSS-TYPE OPEN-WEB OR
 PERFORATED MEMBERS.
 R502.1.2.1 MATERIALS.
 DRAFTSTOPPING MATERIALS SHALL NOT BE LESS THAN ?-INCH
 (12.7 MM) GYPSUM BOARD, 3 / 8 -INCH (9.5 MM) WOOD
 STRUCTURAL PANELS, 3 / 8 -INCH (9.5 MM) TYPE 2-M-W
 PARTICLEBOARD OR OTHER APPROVED MATERIALS ADEQUATELY
 SUPPORTED. DRAFTSTOPPING SHALL BE INSTALLED PARALLEL TO
 THE FLOOR FRAMING MEMBERS UNLESS OTHERWISE APPROVED BY
 THE BUILDING OFFICIAL. THE INTEGRITY OF ALL DRAFTSTOPS
 SHALL BE MAINTAINED.
  
 7) PROVIDE A WINDOW SCHEDULE. SPECIFY THE WINDOW TYPE,
 SIZE AND LOCATION. FBC 106.1.1* CITY AMENDMENTS.
  
 8) THE WALL LEGEND ON A-1.1 AND A-1.2 SPECIFY WOOD
 FRAME EXTERIOR WALLS. HOWEVER, WALL SECTION 3 ON A-5.1
 SPECIFIES METAL STUDS ON THE SECOND FLOOR AT THIS
 LOCATION. PLEASE CORRECT. FBC 106.1.1* CITY
 AMENDMENTS.
  
 9) WALL TYPE B ON DETAIL 2 ON A-1.1 IS 3-5/8" 20 GA.
 METAL STUDS AND THE STRUCTURAL DRAWINGS SHOW WOOD FRAME
 BEARING WALLS. PLEASE CLARIFY. FBC 106.1.1* CITY
 AMENDMENTS.
  
 10) ON SHEET A-3.2 THE MARK FOR SECTION 3/A-5.1 APPEARS
 TO BE IN THE WRONG LOCATION. PLEASE CORRECT. FBC
 106.1.1* CITY AMENDMENTS.
  
 11) SHOW COMPLIANCE WITH R602.1.2 FIREBLOCKING
 REQUIRED.
 FIREBLOCKING SHALL BE PROVIDED TO CUT OFF ALL CONCEALED
 DRAFT OPENINGS (BOTH VERTICAL AND HORIZONTAL) AND TO
 FORM AN EFFECTIVE FIRE BARRIER BETWEEN STORIES, AND
 BETWEEN A TOP STORY AND THE ROOF SPACE. FIREBLOCKING
 SHALL BE PROVIDED IN WOOD-FRAME CONSTRUCTION IN THE
 FOLLOWING LOCATIONS.
 3. IN CONCEALED SPACES BETWEEN STAIR STRINGERS AT THE
 TOP AND BOTTOM OF THE RUN.
  
 12) DETAIL 8 ON A-6.2 SHOWS INSULATION AT THE CEILING
 AND THE WALL SECTION ON A-5.1 SPECIFIES ICYNENE
 INSULATION. PLEASE CLARIFY.FBC 106.1.1* CITY
 AMENDMENTS.
  
 13) STRUCTURAL NOTE D-2 ON ON S-1 INCORRECTLY SPECIFIES
 ASCE 7-05. ASCE 7-02 IS THE EDITION THAT IS REFERENCED
 BY THE 2004 FBC. PLEASE CORRECT. SEE FBC R CHAPTER 43.
  
 14) PROVIDE WINDOW AND DOOR BUCK DETAILS. SPECIFY THE
 FASTENERS AND SPACING.FBC 106.1.2* CITY AMENDMENTS.
  
 15) ON DETAIL 8 ON A-6.1, SPECIFY THE EMBED DEPTH OF
 THE 1/2 " BOLTS FOR THE GARAGE DOOR BUCKS. FBC 106.1.1*
 CITY AMENDMENTS.
  
 16) THE BOTTOM PORTION OF THE FIRST FLOOR DOOR SCHEDULE
 ON SHEET A-6.1 IS MISSING.
  
 17) SUBMIT TWO COPIES OF THE SOIL REPORT WITH THE
 EMBOSSED SEAL AND ORIGINAL SIGNATURE OF THE SOIL
 ENGINEER. SEE FS 471 AND FAC 61G15-23.002.
  
 18) THE A/C AREA ON THE ENERGY CALCULATION FORMS DO NOT
 CORRESPOND WITH THE PLANS. THE OWNER/AGENT IS REQUIRED
 TO SIGN AND DATE THE FORM. SEE FBC CHAPTER 13-6.
  
 19) ON S-2 THE UPLIFT VALUE SPECIFIED FOR THE SIMPSON
 H-1 IS INCORRECT. THE UPLIFT VALUE SHOULD BE 585# PER
 THE 2007 SIMPSON CATALOG.
  
 20) SPECIFY THE MAXIMUM SPACING OF THE VERTICAL WALL
 REINFORCING ON THE PLANS. FBC 106.1.2* CITY
 AMENDMENTS.
  
 21) ON SHEET S-4 THE MARK FOR 3/S-7 IS LOCATED WHERE
 THE FLOOR TRUSSES ARE PARALLEL TO THE CONCRETE BEAM AND
 DETAIL 3 ON S-7 SHOWS THE TRUSSES PERPENDICULAR TO THE
 CONCRETE BEAM. PLEASE CORRECT.
  
 22) ON S-5 THE UPLIFT FOR THE TRUSSES AT THE REAR PORCH
 ARE SPECIFIED AS 2237#, HOWEVER THE "C" CONNECTORS
 SPECIFIED ARE RATED FOR AN UPLIFT OF 1260#. PLEASE
 CORRECT. FBC 106.1.1* CITY AMENDMENTS.
  
 23) SPECIFY THE CONNECTORS FOR THE 2 PLY GIRDERS AT THE
 EXTERIOR MASONRY WALL AT THE REAR PORCH. FBC 106.1.2*
 CITY AMENDMENTS.
  
 24) SPECIFY THE CONNECTORS FOR THE 2 PLY GIRDERS AT THE
 EXTERIOR WOOD FRAME WALL AT THE FRONT PORCH. FBC
 106.1.2* CITY AMENDMENTS.
  
 25) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 ICYNENE INSULATION. FBC 106.1.1* CITY AMENDMENTS.
  
 26)FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS.
 THOSE PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 27) THE SCHEDULE ON A-6.1 SPECIFIES A WOOD DOOR AT THE
 SIDE OF THE GARAGE, BUT THE PRODUCT APPROVAL THAT WAS
 SUBMITTED IS FOR A STEEL DOOR. PLEASE CORRECT. SEE FAC
 RULE 9B-72.
  
 28) THE NOTE ON THE DOOR SCHEDULE ON A-6 STATES THAT
 ALL FRENCH DOORS ARE ALUMINUM AND THEN SPECIFIES WOOD
 DOORS. PLEASE CLARIFY.
  
 29) SUBMIT PRODUCT APPROVALS FOR THE SINGLE INSWING
 FRENCH DOOR AS REQUIRED BY FAC RULE 9B-72.
  
 30) PLEASE CLARIFY THE WINDOW TYPES ON THE PLANS. A
 PRODUCT APPROVAL WAS SUBMITTED FOR CASEMENT WINDOWS AND
 THERE DOES NOT APPEAR TO BE ANY ON THE PLANS.
  
 31) ON SHEET A-6.1 ONE OF THE ELEVATIONS APPEARS TO
 SHOW (2) FIXED WINDOWS MULLED TOGETHER. SUBMIT PRODUCT
 APPROVALS FOR THEM AS REQUIRED BY FAC RULE 9B-72.
  
 32) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 FRONT ENTRY DOOR IS FOR AN OUTSWING DOOR, HOWEVER, THE
 PLANS SHOW THIS DOOR AS AN INSWING DOOR. PLEASE
 CORRECT.
  
 33) THE MAXIMUM WIDTH LISTED IN THE PRODUCT APPROVAL
 FOR THE FRENCH WOOD SIDELITES IS 18-13/16", WHICH DOES
 NOT APPEAR TO BE WIDE ENOUGH TO WORK FOR THE FRONT
 ENTRY ASSEMBLY DIMENSIONS ON THE PLANS. PLEASE REVIEW.
  
 NOTE: IN ORDER TO EXPEDITE PLAN REVIEW PLEASE RETURN
 ONE SET OF THE OLD PLAN SHEETS AND A RESPONSE LETTER
 INDICATING HOW THE PLAN REVIEW COMMENTS HAVE BEEN
 ADDRESSED.
  
  
  
  
  
  
  
  
  
  
  
  