Plan Review Notes For Permit 07100501 |
Permit Number |
07100501 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-10-29 13:16:42 | *****DENIED***** | | | | | | | | 1.THE PROJECT SITE LOCATION SHALL BE IN THE TITLE | | BLOCK OF EACH SUBMITTED PLAN SHEET. | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 3.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | REFERENCED. | | | | 4.SPECIFY THE INTERIOR FINISH MATERIAL FOR THE NEW | | WALL IN TERMS OF CLASS A, CLAAS B, OR CLASS C. | | | | 5.PLEASE SHOW PATH OF TRAVEL AISLE CLEARANCE ONCE THE | | WALL IS ERECTED. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS | | ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|