2007-10-29 09:42:12 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR
 DEVICES. 106.3.5 FBC.
  
 2} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE
 PLANS PER 106.1.1 FBC AS AMENDED.
  
 3} PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE
 BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE
 CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE
 ARTICLE.NOTE SAME ON THE PLAN.
  
 4} AN ELECTRICAL PERMIT IS REQUIRED PER 105.1 FBC AS
 AMENDED.
  
 5} INDICATE COMPLIANCE WITH 210.8(B)(2), GFCI ON THE
 PLAN.
  
 6} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  