2007-10-23 18:53:14****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.COMMERCIAL PROJECTS DO NOT FALL UNDER THE
 EXCEPTIONS TO ARCHITECTURE, FS481.229.PROVIDE PLANS
 PREPARED BY A DESIGN PROFESSIONAL (ARCHITECT OR
 ENGINEER).
  
 2.PLANS ARE TO INCLUDE ALL INFORMATION REQUIRED TO
 SHOW CODE COMPLIANCE.PLANS DID NOT PROVIDE ANY
 INFORMATION.
  
 3.DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3.
  
 4.SHOW HOW EGRESS WILL BE AFFECTED.PROVIDE ALL
 DIMENSIONS.FBC CHAPTER 10.
  
 5.PROVIDE A CODE SUMMARY REGARDING THE EXISTING
 BUILDING; BUILDING TYPE FBC6, BUILDING HEIGHT AND AREA
 FBC5, SPRINKLER INFORMATION, OCCUPANCY CLASSIFICATION
 FBC 3 AND AREA PER OCCUPANCY.
  
 6.PROVIDE AN ARCHITECTURAL QUALITY DETAIL FOR THE
 KNEE WALL, DRAWN TO SCALE, FBC*106.NO DIMENSIONS FOR
 FRAMING MATERIAL OR FASTENERS WAS PROVIDED.
  
 7.PROVIDE A LEGEND.CIRCLES ARE SHOWN ON THE NEW
 WALL, BUT IT IS NOT CLEAR WHAT THEY REPRESENT.ARE
 THEY OUTLETS?TWO DIFFERENT CIRCLE GRAPHICS ARE SHOWN.
  
  
 8.A PORTION OF THE WALL WAS HIGHLIGHTED.HIGHLIGHTER
 CANNOT BE USED TO SHOW CODE COMPLIANCE AS IT DOES NOT
 APPEAR WHEN SCANNED.USE STANDARD ARCHITECTURAL
 GRAPHICS AND MARKERS.
  
 9.SHOW HOW ACCESSIBILITY WILL BE AFFECTED.A
 SWINGING DOOR IS SHOWN WITH NO DIMENSIONS OR OTHER
 INFORMATION, FBC11-4.13.
  