2007-11-19 11:11:26 | REVIEW #: 1ST |
| ACTION: DENIED |
| |
| FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| 1. THE DESIGN PROFESSIONAL OR THE OWNER MUST ELECT ONE |
| OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| SECTIONS 303, 304 AND 305 OF THIS CODE IN ACCORDANCE |
| WITH FBC, EB 301.5. PLEASE DECLARE LEVEL OF ALTERATION |
| UNDER THE ?GENERAL BUILDING CODE ANALYSIS? SECTION ON |
| PLANS. |
| |
| 2. THIS APPEARS TO BE A LEVEL 2 ALTERATION AS DESCRIBED |
| IN FBC, EB 304.1. AS SUCH THE SPACE BEING RECONFIGURED |
| SHALL BE SHOWN TO MEET THE MINIMUM VENTILATION |
| REQUIREMENTS OF FBC,M TABLE 403.3 IN ACCORDANCE WITH |
| FBC,M 609.1. SHOW OUTSIDE AIR CALCULATIONS FOR ALL |
| SPACES AS WELL AS MEANS OF PROVIDING THE REQUIRED RATES |
| OF VENTILATION, INCLUDING BATHROOMS IN ACCORDANCE WITH |
| THESE SECTIONS. |
| |
| 3. MECHANICAL EQUIPMENT AND SUPPORTS THAT ARE EXPOSED |
| TO WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE |
| WIND PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS |
| DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING |
| CODE, BUILDING PER FBC, M 301.13. PROVIDE WIND LOAD |
| CALCULATIONS SHOWING THE ATTACHMENT DETAILS ON PLAN TO |
| BE SUFFICIENT FOR THE REQUIRED WIND LOADS PER FBC SEC. |
| 1609. ALSO, PROVIDE MANUFACTURER?S DATA SHOWING THE |
| EQUIPMENT TO BE DESIGNED FOR WIND LOADS AS REQUIRED BY |
| THESE SECTIONS. |
| |
| 4. ALTERATIONS SUBJECT TO THIS CHAPTER SHALL COMPLY |
| WITH THE REQUIREMENTS OF CHAPTER 13 OF THE FLORIDA |
| BUILDING CODE, BUILDING IN ACCORDANCE WITH FBC, EB |
| 611.1. SHOW COMPLIANCE WITH THE FOLLOWING REQUIREMENTS |
| OF THE FLORIDA ENERGY EFFICIENCY CODE: |
| |
| A) NEWLY INSTALLED EQUIPMENT SHALL MEET THE MINIMUM |
| EFFICIENCY STANDARDS AS LISTED IN FBC TABLE |
| 13-407.1.ABC.3.2A. THE EQUIPMENT LISTED AND THE |
| EFFICIENCY STATED ON PLANS DOES NOT APPEAR TO MEET THIS |
| REQUIREMENT. |
| |
| B) IF ALL WORK ON THIS BUILDING WITHIN A ONE YEAR |
| PERIOD SHOULD MEET THE THRESHOLD FOR A RENOVATION AS |
| DEFINED IN FBC 13-202, COOLING LOAD CALCULATIONS SHALL |
| BE REQUIRED IN ACCORDANCE WITH FBC 13-407.1.ABC.1. |
| |
| C) PROVIDE SHUTOFF DAMPER CONTROLS IN ACCORDANCE WITH |
| FBC 13-409.1.ABC.3.3. |
| |
| 5. CONDENSATE FROM ALL COOLING COILS AND EVAPORATORS |
| SHALL BE CONVEYED FROM THE DRAIN PAN OUTLET TO AN |
| APPROVED PLACE OF DISPOSAL. CONDENSATE SHALL NOT |
| DISCHARGE INTO A STREET, ALLEY OR OTHER AREAS SO AS TO |
| CAUSE A NUISANCE. ALSO, CONDENSATE LINES AND ROOF |
| DOWNSPOUTS SHALL DISCHARGE AT LEAST 1 FOOT (305 MM) |
| AWAY FROM THE STRUCTURE SIDEWALL. SHOW MEANS AND |
| LOCATION OF CONDENSATE DISPOSAL IN COMPLIANCE WITH FBC, |
| M 307.2.1 AND FBC 1503.6. |
| |
| 6. AUXILIARY DRAIN PROTECTION IS REQUIRED IN ACCORDANCE |
| WITH FBC, M 307.2.3. SHOW COMPLIANCE WITH THIS SECTION. |
| A WATER LEVEL DETECTION DEVICE, SUCH AS A FLOAT SWITCH, |
| MAY BE INSTALLED ON THE PRIMARY DRAIN PAN OF THE UNIT |
| AS STATED IN FBC, M 307.2.3(2). |
| |
| 7. RTU DETAIL CALLS FOR ?CYLINDRICAL METALLIC DUCTS? |
| WHILE THE AIR CONDITIONING NOTES CALL FOR RIGID DUCT |
| BOARD AND FLEX. PLEASE COORDINATE DETAILS AND NOTES. |
| FBC, M601.1 AND FBC 106.1.1. |
| |