2007-11-19 11:11:26REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THE DESIGN PROFESSIONAL OR THE OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE IN ACCORDANCE
 WITH FBC, EB 301.5. PLEASE DECLARE LEVEL OF ALTERATION
 UNDER THE ?GENERAL BUILDING CODE ANALYSIS? SECTION ON
 PLANS.
  
 2. THIS APPEARS TO BE A LEVEL 2 ALTERATION AS DESCRIBED
 IN FBC, EB 304.1. AS SUCH THE SPACE BEING RECONFIGURED
 SHALL BE SHOWN TO MEET THE MINIMUM VENTILATION
 REQUIREMENTS OF FBC,M TABLE 403.3 IN ACCORDANCE WITH
 FBC,M 609.1. SHOW OUTSIDE AIR CALCULATIONS FOR ALL
 SPACES AS WELL AS MEANS OF PROVIDING THE REQUIRED RATES
 OF VENTILATION, INCLUDING BATHROOMS IN ACCORDANCE WITH
 THESE SECTIONS.
  
 3. MECHANICAL EQUIPMENT AND SUPPORTS THAT ARE EXPOSED
 TO WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE
 WIND PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS
 DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING PER FBC, M 301.13. PROVIDE WIND LOAD
 CALCULATIONS SHOWING THE ATTACHMENT DETAILS ON PLAN TO
 BE SUFFICIENT FOR THE REQUIRED WIND LOADS PER FBC SEC.
 1609. ALSO, PROVIDE MANUFACTURER?S DATA SHOWING THE
 EQUIPMENT TO BE DESIGNED FOR WIND LOADS AS REQUIRED BY
 THESE SECTIONS.
  
 4. ALTERATIONS SUBJECT TO THIS CHAPTER SHALL COMPLY
 WITH THE REQUIREMENTS OF CHAPTER 13 OF THE FLORIDA
 BUILDING CODE, BUILDING IN ACCORDANCE WITH FBC, EB
 611.1. SHOW COMPLIANCE WITH THE FOLLOWING REQUIREMENTS
 OF THE FLORIDA ENERGY EFFICIENCY CODE:
  
 A) NEWLY INSTALLED EQUIPMENT SHALL MEET THE MINIMUM
 EFFICIENCY STANDARDS AS LISTED IN FBC TABLE
 13-407.1.ABC.3.2A. THE EQUIPMENT LISTED AND THE
 EFFICIENCY STATED ON PLANS DOES NOT APPEAR TO MEET THIS
 REQUIREMENT.
  
 B) IF ALL WORK ON THIS BUILDING WITHIN A ONE YEAR
 PERIOD SHOULD MEET THE THRESHOLD FOR A RENOVATION AS
 DEFINED IN FBC 13-202, COOLING LOAD CALCULATIONS SHALL
 BE REQUIRED IN ACCORDANCE WITH FBC 13-407.1.ABC.1.
  
 C) PROVIDE SHUTOFF DAMPER CONTROLS IN ACCORDANCE WITH
 FBC 13-409.1.ABC.3.3.
  
 5. CONDENSATE FROM ALL COOLING COILS AND EVAPORATORS
 SHALL BE CONVEYED FROM THE DRAIN PAN OUTLET TO AN
 APPROVED PLACE OF DISPOSAL. CONDENSATE SHALL NOT
 DISCHARGE INTO A STREET, ALLEY OR OTHER AREAS SO AS TO
 CAUSE A NUISANCE. ALSO, CONDENSATE LINES AND ROOF
 DOWNSPOUTS SHALL DISCHARGE AT LEAST 1 FOOT (305 MM)
 AWAY FROM THE STRUCTURE SIDEWALL. SHOW MEANS AND
 LOCATION OF CONDENSATE DISPOSAL IN COMPLIANCE WITH FBC,
 M 307.2.1 AND FBC 1503.6.
  
 6. AUXILIARY DRAIN PROTECTION IS REQUIRED IN ACCORDANCE
 WITH FBC, M 307.2.3. SHOW COMPLIANCE WITH THIS SECTION.
 A WATER LEVEL DETECTION DEVICE, SUCH AS A FLOAT SWITCH,
 MAY BE INSTALLED ON THE PRIMARY DRAIN PAN OF THE UNIT
 AS STATED IN FBC, M 307.2.3(2).
  
 7. RTU DETAIL CALLS FOR ?CYLINDRICAL METALLIC DUCTS?
 WHILE THE AIR CONDITIONING NOTES CALL FOR RIGID DUCT
 BOARD AND FLEX. PLEASE COORDINATE DETAILS AND NOTES.
 FBC, M601.1 AND FBC 106.1.1.
  