2007-11-14 09:47:151. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER SYSTEM REMODEL.
  
 3. THE NEW TENANT PARTITIONS SHOULD BE CALLED OUT ON
 THE PLANS AS ONE HOUR FIRE RATED TENANT DEMISING WALLS
 AS INDICATED IN THE WALL DETAIL.
  
 4. PORTABLE FIRE EXTINGUISHERS ILLUSTRATED ON PLANS
 SHALL BE CURRENTLY SERVICE TAGGED.
  
 5. ALL FUTURE TENANT BUILD-OUT SPACES SHALL BE EQUIPPED
 WITH EMERGENCY LIGHTING EQUIPMENT.
  
 6. ADDITIONAL PORTABLE FIRE EXTINGUISHERS WILL BE
 NEEDED IN FUTURE TENANT SPACES DUE TO TRAVEL
 DISTANCES.
  
 7. AN ADDITIONAL EXIT SIGN IS NEEDED NEAR SUITE C TO
 DIRECT PERSONS AROUND CORNER TO THE EXIT.
  
 8. WHAT IS THE AJACENT TENANT SPACE USED FOR. HOW MANY
 TOTAL PERSONS ARE EXPECTED AT THE BUILDING.
  
 9. IS THERE ANY FIRE ALARM EQUIPMENT PRESENT AT THE
 BUILDING.
  
 10. MORE DETAILS NEEDED ON GLASS FIRE RATED DOORS
 ILLUSTRATED ON THE PLANS.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX