Plan Review Notes For Permit 07100482 |
Permit Number |
07100482 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-11-14 09:47:15 | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | WITH NFPA 241. | | | | 2. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE | | SPRINKLER SYSTEM REMODEL. | | | | 3. THE NEW TENANT PARTITIONS SHOULD BE CALLED OUT ON | | THE PLANS AS ONE HOUR FIRE RATED TENANT DEMISING WALLS | | AS INDICATED IN THE WALL DETAIL. | | | | 4. PORTABLE FIRE EXTINGUISHERS ILLUSTRATED ON PLANS | | SHALL BE CURRENTLY SERVICE TAGGED. | | | | 5. ALL FUTURE TENANT BUILD-OUT SPACES SHALL BE EQUIPPED | | WITH EMERGENCY LIGHTING EQUIPMENT. | | | | 6. ADDITIONAL PORTABLE FIRE EXTINGUISHERS WILL BE | | NEEDED IN FUTURE TENANT SPACES DUE TO TRAVEL | | DISTANCES. | | | | 7. AN ADDITIONAL EXIT SIGN IS NEEDED NEAR SUITE C TO | | DIRECT PERSONS AROUND CORNER TO THE EXIT. | | | | 8. WHAT IS THE AJACENT TENANT SPACE USED FOR. HOW MANY | | TOTAL PERSONS ARE EXPECTED AT THE BUILDING. | | | | 9. IS THERE ANY FIRE ALARM EQUIPMENT PRESENT AT THE | | BUILDING. | | | | 10. MORE DETAILS NEEDED ON GLASS FIRE RATED DOORS | | ILLUSTRATED ON THE PLANS. | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | 804-4709 PHONE | | 804-4774 FAX |
|