Plan Review Notes
Plan Review Notes For Permit 07100482
Permit Number 07100482
Review Stop E
Sequence Number 1
Notes
Date Text
2007-11-07 10:12:25** DENIED **
  
 1) NOTE: PLEASE SUBMIT COMPLETE PLANS FOR SCOPE OF
 WORK.
 PLEASE SEE THAT ALL RELEVANT CODES AS FOLLOWS ARE TO BE
 STATED ON DRAWINGS.
 2004 FBC W2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE SUBMIT AN ELECTRICAL RISER COMPLYING
 WITH THE NEC.
 PLEASE SEE 230.2 AS THE SERVICE(S) AS SHOWN ARE NOT
 PERMITTED.
 PLEASE SEE MORE THAN SIX MAINS ARE SHOWN WHICH IS NOT
 PERMITTED. 230.70,230.71,230.72 ETC
 PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR ALL LOADS.
 220.
 PLEASE SEE 110.9 FOR COMPLETE AIC RATINGS FOR ALL.
 PLEASE COMPLETE GROUNDING ELECTRODE SYSTEM(S) AS
 REQUIRED PER 250.50,250.66 ETC
 PLEASE INDICATE ALL CONDUCTORS AND OVER CURRENT
 PROTECTION WHICH COMPLIES WITH THE NEC 310.16, 240.4.
 EXAMPLE: 5/0 CONDUCTORS ARE SHOWN. THERE IS NOT SUCH
 WIRE SIZE BASED ON THE AWG AMERICAN WIRE GAUGE.
  
 ** PLEASE KNOW AS THERE ARE TOO NUMEROUS CHANGES
 REQUIRED A COMPLETE REVIEW FOR CODE COMPLIANCE CAN NOT
 BE DONE AT THIS TIME.
 PLEASE KNOW THE PLANS FOR POSSIBLE BUILD OUT WILL BE
 AFFECTED AS WELL.
  
 3) NOTE: PLEASE SEE 700.12F AS THE CIRCUITING FOR
 EMERGENCY LIGHT FIXTURES SHALL BE CIRCUITED TO THE
 BRANCH CIRCUIT OF THE LOCAL LIGHTING.
  
 4) NOTE: PLEASE COMPLETE PLANS FOR ALL CIRCUITING AND
 INTENDED SCOPE OF WORK,
 FBC 106.3.5.1.2, 106.1.2
  
 5) NOTE: PLEASE SEE NEC 517.1 AS WIRING METHOD FOR THIS
 SPACE IS REQUIRED TO MEET CODE. PLEASE ADJUST PLANS AND
 DESIGN FOR THIS.
  
 6) NOTE: PLEASE SUBMIT COMPLETE INFORMATION FOR FBC
 CHAPTER 13 REQUIREMENTS.
 PLEASE SEE 13-413.1.ABC.1.1, AND .1.2
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3
 PLEASE SEE 13-415.2 FOR LIGHTING PERFORMANCE
 CALCULATIONS.
 ETC
  
 7) NOTE: PLEASE SEE ADDRESSING AS ALL UNIT/SUITE
 NUMBERS WILL BE REQUIRED ON PLANS.
  
 8) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF
 WORK AS SHOWN SHALL INCLUDE ALL LABOR, MATERIALS,
 DESIGN COST, EQUIPMENT ETC EVEN IF ANY OF THIS IS OWNER
 SUPPLIED. THE VALUE FOR SCOPE SHOWN IS LOW.
 FBC 108.3
  
  
 *** PLEASE KNOW AS BASED ON THE MANY CHANGES WHICH WILL
 BE REQUIRED, THERE MAY VERY WELL BE NEW COMMENTS ON THE
 FOLLOWING REVIEW AS THERE ARE MANY ITEMS MISSING FROM
 PLANS. THESE ITEMS AND CHANGES CAN NOT BE REVIEWED AT
 THIS TIME.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]