Date |
Text |
2007-11-07 10:12:25 | ** DENIED ** |
| |
| 1) NOTE: PLEASE SUBMIT COMPLETE PLANS FOR SCOPE OF |
| WORK. |
| PLEASE SEE THAT ALL RELEVANT CODES AS FOLLOWS ARE TO BE |
| STATED ON DRAWINGS. |
| 2004 FBC W2006 REVISIONS. |
| 2005 NFPA-70 |
| 2003 NFPA-101 |
| 2002 NFPA-72 |
| |
| 2) NOTE: PLEASE SUBMIT AN ELECTRICAL RISER COMPLYING |
| WITH THE NEC. |
| PLEASE SEE 230.2 AS THE SERVICE(S) AS SHOWN ARE NOT |
| PERMITTED. |
| PLEASE SEE MORE THAN SIX MAINS ARE SHOWN WHICH IS NOT |
| PERMITTED. 230.70,230.71,230.72 ETC |
| PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR ALL LOADS. |
| 220. |
| PLEASE SEE 110.9 FOR COMPLETE AIC RATINGS FOR ALL. |
| PLEASE COMPLETE GROUNDING ELECTRODE SYSTEM(S) AS |
| REQUIRED PER 250.50,250.66 ETC |
| PLEASE INDICATE ALL CONDUCTORS AND OVER CURRENT |
| PROTECTION WHICH COMPLIES WITH THE NEC 310.16, 240.4. |
| EXAMPLE: 5/0 CONDUCTORS ARE SHOWN. THERE IS NOT SUCH |
| WIRE SIZE BASED ON THE AWG AMERICAN WIRE GAUGE. |
| |
| ** PLEASE KNOW AS THERE ARE TOO NUMEROUS CHANGES |
| REQUIRED A COMPLETE REVIEW FOR CODE COMPLIANCE CAN NOT |
| BE DONE AT THIS TIME. |
| PLEASE KNOW THE PLANS FOR POSSIBLE BUILD OUT WILL BE |
| AFFECTED AS WELL. |
| |
| 3) NOTE: PLEASE SEE 700.12F AS THE CIRCUITING FOR |
| EMERGENCY LIGHT FIXTURES SHALL BE CIRCUITED TO THE |
| BRANCH CIRCUIT OF THE LOCAL LIGHTING. |
| |
| 4) NOTE: PLEASE COMPLETE PLANS FOR ALL CIRCUITING AND |
| INTENDED SCOPE OF WORK, |
| FBC 106.3.5.1.2, 106.1.2 |
| |
| 5) NOTE: PLEASE SEE NEC 517.1 AS WIRING METHOD FOR THIS |
| SPACE IS REQUIRED TO MEET CODE. PLEASE ADJUST PLANS AND |
| DESIGN FOR THIS. |
| |
| 6) NOTE: PLEASE SUBMIT COMPLETE INFORMATION FOR FBC |
| CHAPTER 13 REQUIREMENTS. |
| PLEASE SEE 13-413.1.ABC.1.1, AND .1.2 |
| PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 |
| PLEASE SEE 13-415.2 FOR LIGHTING PERFORMANCE |
| CALCULATIONS. |
| ETC |
| |
| 7) NOTE: PLEASE SEE ADDRESSING AS ALL UNIT/SUITE |
| NUMBERS WILL BE REQUIRED ON PLANS. |
| |
| 8) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF |
| WORK AS SHOWN SHALL INCLUDE ALL LABOR, MATERIALS, |
| DESIGN COST, EQUIPMENT ETC EVEN IF ANY OF THIS IS OWNER |
| SUPPLIED. THE VALUE FOR SCOPE SHOWN IS LOW. |
| FBC 108.3 |
| |
| |
| *** PLEASE KNOW AS BASED ON THE MANY CHANGES WHICH WILL |
| BE REQUIRED, THERE MAY VERY WELL BE NEW COMMENTS ON THE |
| FOLLOWING REVIEW AS THERE ARE MANY ITEMS MISSING FROM |
| PLANS. THESE ITEMS AND CHANGES CAN NOT BE REVIEWED AT |
| THIS TIME. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |