Plan Review Notes
Plan Review Notes For Permit 07100482
Permit Number 07100482
Review Stop B
Sequence Number 1
Notes
Date Text
2007-11-05 16:50:20PROJECT: 2223 PALM BEACH LAKES BLVD.
  
 PROJECT DETAIL: INTERIOR ALTERATION FOR NEW OUTPATIENT
 CLINIC
  
  
 CODE REVIEW:2004 FLORIDA EXISTING BUILDING CODE
 W/2006 REVISIONS.
 2004 FLORIDA BUILDING CODE W/ 2006 REVISIONS.
 CITY OF WEST PALM BEACH/ FLORIDA BUILDING CODE
 ADMINISTRATION AMENDMENTS,
 CHAPTER 1, 2004 EDITION.
  
 STATUS: FAILED
  
  
 COMMENTS:
  
 1) PLEASE CONTACT MR. ALEX ORTEGA WITH THE PALM BEACH
 COUNTY HEALTH DEPARTMENT PRIOR TO ANY DEMOLITION AT
 355.3023,EXT.1148. AN ASBESTOS SURVEY MAY BE REQUIRED
 AS PER THE FOLLOWING:
  
 105.9 ASBESTOS.
 THE ENFORCING AGENCY SHALL REQUIRE EACH BUILDING PERMIT
 FOR THE DEMOLITION OR RENOVATION OF AN EXISTING
 STRUCTURE TO CONTAIN AN ASBESTOS NOTIFICATION STATEMENT
 WHICH INDICATES THE OWNER?S OR OPERATOR?S
 RESPONSIBILITY TO COMPLY WITH THE PROVISIONS OF SECTION
 469.003, FLORIDA STATUTES, AND TO NOTIFY THE DEPARTMENT
 OF ENVIRONMENTAL PROTECTION OF HIS OR HER INTENTIONS TO
 REMOVE ASBESTOS, WHEN APPLICABLE, IN ACCORDANCE WITH
 STATE AND FEDERAL LAW.
  
 2) REQUIRE A NOTICE OF COMMENCEMENT AS PER THE
 FOLLOWING:
  
 FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) AS PER THE FLORIDA EXISTING BUILDING CODE, SECTION
 301.5:
  
 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO SECTION
 303,304 & 305 OF THIS CODE.
  
 4) PLEASE SATISFY PREVIOUS ADDRESSING REQUIREMENTS.
  
 5) PROVIDE FIRE EXTINGUISHERS AS REQUIRED:
  
 SECTION 1309
 FIRE EXTINGUISHERS
 1309.1WHERE REQUIRED.
 ALL STRUCTURES UNDER CONSTRUCTION, ALTERATION OR
 DEMOLITION SHALL BE PROVIDED WITH NOT LESS THAN ONE
 APPROVED PORTABLE FIRE EXTINGUISHER IN ACCORDANCE WITH
 SECTION 906 OF THE FLORIDA BUILDING CODE, BUILDING AND
 SIZED FOR NOT LESS THAN ORDINARY HAZARD AS FOLLOWS:
 1. AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE
 COMBUSTIBLE MATERIALS HAVE ACCUMULATE
 2. IN EVERY STORAGE AND CONSTRUCTION SHED.
 3. ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE
 PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE
 STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS.
  
 6) PLEASE PROVIDE PRODUCT APPROVALS/ENGINEERING FOR THE
 FOLLOWING:
  
 A) SPECIFICATIONS FOR 1 HOUR RATED GLASS DOOR AND
 STOREFRONT FRAMING SYSTEM.(MARK A).
 B) 1 HOUR RATED DOOR.( MARK B).
 C) DOOR INDICATED AT MARK E.
 D) EXIT DOOR AT WEST BUILDING ELEVATION.
 E) PRE-CAST CONCRETE LINTELS.
  
 7) PROVIDE CLARIFICATION FOR THE FOLLOWING STATEMENT:
  
 *TENANT EXITS UNDER SEPARATE PERMIT, SHEET A-3.
  
 8) PLEASE PROVIDE ENERGY CALCULATIONS AS PER THE
 FOLLOWING:
  
 FLORIDA EXISTING BUILDING CODE
  
 SECTION 611
 ENERGY CONSERVATION
 611.1MINIMUM REQUIREMENTS.
 ALTERATIONS SUBJECT TO THIS CHAPTER SHALL COMPLY
 WITH THE REQUIREMENTS OF CHAPTER 13 OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
  
 9) SIZE OF RATED GLAZING SHALL MEET THE NFPA80
 STANDARDS AS PER THE FBC, PLEASE INDICATE THE TOTAL
 SQUARE AREA OF GLAZING PER UNIT:
  
 715.4.4 NONWIRED GLASS.
 GLAZING OTHER THAN WIRED GLASS IN FIRE WINDOW
 ASSEMBLIES SHALL BE FIRE-PROTECTION-RATED GLAZING
 INSTALLED IN ACCORDANCE WITH AND COMPLYING WITH THE
 SIZE LIMITATIONS SET FORTH IN NFPA 80.
  
 10) PLEASE SUBMIT EPOXY AND CONCRETE SPECIFICATIONS.
  
 11) PLEASE PROVIDE DETAIL SECTION NUMBER AT 14' ROUGH
 OPENING.
  
 12) WHERE IS DETAIL 2A/A-2??
  
 13) MARK E MEANS EXISTING ON SHEET A-3? PLEASE CLARIFY
 DOOR SCHEDULE.
  
 14) PLEASE PROVIDE LISTED AND APPROVED FIRESTOPPING
 ASSEMBLY DETAILS FOR THROUGH PENETRATIONS:
  
 FLORIDA BUILDING CODE
  
 712.3.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM. THROUGH
 PENETRATIONS SHALL BE PROTECTED BY AN APPROVED
 PENETRATION FIRESTOP SYSTEM INSTALLED AS TESTED IN
 ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A MINIMUM
 POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA)
 OF WATER AND SHALL HAVE AN F RATING OF NOT LESS THAN
 THE REQUIRED FIRE-RESISTANCE RATING OF THE WALL
 PENETRATED.
  
 15) AS PER THE FLORIDA EXISTING BUILDING CODE, SECTION
 605.4.1.1, AN ADDITIONAL EXIT IS REQUIRED FOR SUITE
 "B":
  
 605.4.1.1OCCUPANT LOAD AND TRAVEL DISTANCE.
  
 IN ANY WORK AREA, ALL ROOMS AND SPACES HAVING AN
 OCCUPANT LOAD GREATER THAN 50 OR IN WHICH THE TRAVEL
 DISTANCE TO AN EXIT EXCEEDS 75 FEET (22 860 MM) SHALL
 HAVE A MINIMUM OF TWOEGRESS DOORWAYS.
 EXCEPTION: STORAGE ROOMS IN GROUP S1 AND S2 OCCUPANCIES
 HAVING A MAXIMUM OCCUPANT LOAD OF 10.
  
 16) PLEASE PROVIDE DETAILS FOR THE EXISTING BATHROOMS.
 A BUILDING THAT IS ALTERED SHALL COMPLY WITH FBC,
 CHAPTER 11:
  
 606.1GENERAL.
 A BUILDING, FACILITY, OR ELEMENT THAT IS ALTERED SHALL
 COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE,
 BUILDING.
  
 17) THE VALUATION FOR THE PROPOSED SCOPE OF WORK
 APPEARS TO BE LOW AND SHOULD BE ADJUSTED TO REFLECT THE
 SAME.
  
 *********END OF REVIEW********
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  