2007-11-05 16:50:20 | PROJECT: 2223 PALM BEACH LAKES BLVD. |
| |
| PROJECT DETAIL: INTERIOR ALTERATION FOR NEW OUTPATIENT |
| CLINIC |
| |
| |
| CODE REVIEW:2004 FLORIDA EXISTING BUILDING CODE |
| W/2006 REVISIONS. |
| 2004 FLORIDA BUILDING CODE W/ 2006 REVISIONS. |
| CITY OF WEST PALM BEACH/ FLORIDA BUILDING CODE |
| ADMINISTRATION AMENDMENTS, |
| CHAPTER 1, 2004 EDITION. |
| |
| STATUS: FAILED |
| |
| |
| COMMENTS: |
| |
| 1) PLEASE CONTACT MR. ALEX ORTEGA WITH THE PALM BEACH |
| COUNTY HEALTH DEPARTMENT PRIOR TO ANY DEMOLITION AT |
| 355.3023,EXT.1148. AN ASBESTOS SURVEY MAY BE REQUIRED |
| AS PER THE FOLLOWING: |
| |
| 105.9 ASBESTOS. |
| THE ENFORCING AGENCY SHALL REQUIRE EACH BUILDING PERMIT |
| FOR THE DEMOLITION OR RENOVATION OF AN EXISTING |
| STRUCTURE TO CONTAIN AN ASBESTOS NOTIFICATION STATEMENT |
| WHICH INDICATES THE OWNER?S OR OPERATOR?S |
| RESPONSIBILITY TO COMPLY WITH THE PROVISIONS OF SECTION |
| 469.003, FLORIDA STATUTES, AND TO NOTIFY THE DEPARTMENT |
| OF ENVIRONMENTAL PROTECTION OF HIS OR HER INTENTIONS TO |
| REMOVE ASBESTOS, WHEN APPLICABLE, IN ACCORDANCE WITH |
| STATE AND FEDERAL LAW. |
| |
| 2) REQUIRE A NOTICE OF COMMENCEMENT AS PER THE |
| FOLLOWING: |
| |
| FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 3) AS PER THE FLORIDA EXISTING BUILDING CODE, SECTION |
| 301.5: |
| |
| A DESIGN PROFESSIONAL OR AN |
| OWNER MUST ELECT ONE OR A COMBINATION OF |
| LEVELS OF ALTERATION PURSUANT TO SECTION |
| 303,304 & 305 OF THIS CODE. |
| |
| 4) PLEASE SATISFY PREVIOUS ADDRESSING REQUIREMENTS. |
| |
| 5) PROVIDE FIRE EXTINGUISHERS AS REQUIRED: |
| |
| SECTION 1309 |
| FIRE EXTINGUISHERS |
| 1309.1WHERE REQUIRED. |
| ALL STRUCTURES UNDER CONSTRUCTION, ALTERATION OR |
| DEMOLITION SHALL BE PROVIDED WITH NOT LESS THAN ONE |
| APPROVED PORTABLE FIRE EXTINGUISHER IN ACCORDANCE WITH |
| SECTION 906 OF THE FLORIDA BUILDING CODE, BUILDING AND |
| SIZED FOR NOT LESS THAN ORDINARY HAZARD AS FOLLOWS: |
| 1. AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE |
| COMBUSTIBLE MATERIALS HAVE ACCUMULATE |
| 2. IN EVERY STORAGE AND CONSTRUCTION SHED. |
| 3. ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE |
| PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE |
| STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS. |
| |
| 6) PLEASE PROVIDE PRODUCT APPROVALS/ENGINEERING FOR THE |
| FOLLOWING: |
| |
| A) SPECIFICATIONS FOR 1 HOUR RATED GLASS DOOR AND |
| STOREFRONT FRAMING SYSTEM.(MARK A). |
| B) 1 HOUR RATED DOOR.( MARK B). |
| C) DOOR INDICATED AT MARK E. |
| D) EXIT DOOR AT WEST BUILDING ELEVATION. |
| E) PRE-CAST CONCRETE LINTELS. |
| |
| 7) PROVIDE CLARIFICATION FOR THE FOLLOWING STATEMENT: |
| |
| *TENANT EXITS UNDER SEPARATE PERMIT, SHEET A-3. |
| |
| 8) PLEASE PROVIDE ENERGY CALCULATIONS AS PER THE |
| FOLLOWING: |
| |
| FLORIDA EXISTING BUILDING CODE |
| |
| SECTION 611 |
| ENERGY CONSERVATION |
| 611.1MINIMUM REQUIREMENTS. |
| ALTERATIONS SUBJECT TO THIS CHAPTER SHALL COMPLY |
| WITH THE REQUIREMENTS OF CHAPTER 13 OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| |
| 9) SIZE OF RATED GLAZING SHALL MEET THE NFPA80 |
| STANDARDS AS PER THE FBC, PLEASE INDICATE THE TOTAL |
| SQUARE AREA OF GLAZING PER UNIT: |
| |
| 715.4.4 NONWIRED GLASS. |
| GLAZING OTHER THAN WIRED GLASS IN FIRE WINDOW |
| ASSEMBLIES SHALL BE FIRE-PROTECTION-RATED GLAZING |
| INSTALLED IN ACCORDANCE WITH AND COMPLYING WITH THE |
| SIZE LIMITATIONS SET FORTH IN NFPA 80. |
| |
| 10) PLEASE SUBMIT EPOXY AND CONCRETE SPECIFICATIONS. |
| |
| 11) PLEASE PROVIDE DETAIL SECTION NUMBER AT 14' ROUGH |
| OPENING. |
| |
| 12) WHERE IS DETAIL 2A/A-2?? |
| |
| 13) MARK E MEANS EXISTING ON SHEET A-3? PLEASE CLARIFY |
| DOOR SCHEDULE. |
| |
| 14) PLEASE PROVIDE LISTED AND APPROVED FIRESTOPPING |
| ASSEMBLY DETAILS FOR THROUGH PENETRATIONS: |
| |
| FLORIDA BUILDING CODE |
| |
| 712.3.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM. THROUGH |
| PENETRATIONS SHALL BE PROTECTED BY AN APPROVED |
| PENETRATION FIRESTOP SYSTEM INSTALLED AS TESTED IN |
| ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A MINIMUM |
| POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA) |
| OF WATER AND SHALL HAVE AN F RATING OF NOT LESS THAN |
| THE REQUIRED FIRE-RESISTANCE RATING OF THE WALL |
| PENETRATED. |
| |
| 15) AS PER THE FLORIDA EXISTING BUILDING CODE, SECTION |
| 605.4.1.1, AN ADDITIONAL EXIT IS REQUIRED FOR SUITE |
| "B": |
| |
| 605.4.1.1OCCUPANT LOAD AND TRAVEL DISTANCE. |
| |
| IN ANY WORK AREA, ALL ROOMS AND SPACES HAVING AN |
| OCCUPANT LOAD GREATER THAN 50 OR IN WHICH THE TRAVEL |
| DISTANCE TO AN EXIT EXCEEDS 75 FEET (22 860 MM) SHALL |
| HAVE A MINIMUM OF TWOEGRESS DOORWAYS. |
| EXCEPTION: STORAGE ROOMS IN GROUP S1 AND S2 OCCUPANCIES |
| HAVING A MAXIMUM OCCUPANT LOAD OF 10. |
| |
| 16) PLEASE PROVIDE DETAILS FOR THE EXISTING BATHROOMS. |
| A BUILDING THAT IS ALTERED SHALL COMPLY WITH FBC, |
| CHAPTER 11: |
| |
| 606.1GENERAL. |
| A BUILDING, FACILITY, OR ELEMENT THAT IS ALTERED SHALL |
| COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE, |
| BUILDING. |
| |
| 17) THE VALUATION FOR THE PROPOSED SCOPE OF WORK |
| APPEARS TO BE LOW AND SHOULD BE ADJUSTED TO REFLECT THE |
| SAME. |
| |
| *********END OF REVIEW******** |
| |
| PLAN REVIEW: KEN CONRAD |