Plan Review Notes For Permit 07100467 |
Permit Number |
07100467 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-10-29 12:43:56 | *****DENIED***** | | | | | | 1.THE SUITE NUMBER SHALL BE INCLUDED IN THE ADDRESS | | OF THE PROJECT SITE LOCATED IN THE TITLE BLOCK OF EACH | | SUBMITTED PLAN SHEET. | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 3.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER | | ACCESS TO / EGRESS FROM THE THIRD FLOOR OR THE | | BUILDING.ALL EXIT COMPONENTS ARE TO BE MAINTAINED. | | | | 4.THE DIRECTIONAL ARROW ON SHEET A.2 DOES NOT | | CORRELATE WITH THAT SHOWN ON THE A.1 SHEET. | | | | 5.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | REFERENCED. | | | | 6. SHOW THE LOCATION OF THE EXIT LIGHT(S), EMERGENCY | | LIGHT(S), AND THE 2A:10BC RATED FIRE EXTINGUISHER FOR | | THE PROPOSED THIRD FLOOR PLAN. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATNG WHERE ON THE PLAN EACH ITEM WAS | | ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|