Plan Review Notes
Plan Review Notes For Permit 07100467
Permit Number 07100467
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-25 08:29:30***DENIED ***
  
 1) NOTE: PLEASE INDICATE NEW LIGHTING CONTROL DEVICES
 FOR NEW LIGHTING CONTROLS BEING INSTALLED PER
 13-415.1.ABC.1.1, .1.2.
  
 2) NOTE: PLEASE CLARIFY LOCATIONS OF ANY EMERGENCY
 LIGHTING FIXTURES AS REQUIRED PER LS 101 7.8 AND 7.9.
 PLEASE SEE COMMON EXIT ACCESS AREAS.
 PLEASE BE SURE TO CIRCUIT PER 700.12F.
  
 3) NOTE: PLEASE SEE THE PLANS INDICATE NEW CIRCUITS
 HOWEVER NO PANEL SCHEDULE/DESIGNATION WAS SUBMITTED.
 408.4.
 FBC 106.1.2 PLEASE SUBMIT.
  
 4) NOTE: PLEASE SEE THE VALUE FOR THE SCOPE OF WORK AS
 SHOWN IS LOW BASED ON SCOPE.
 FBC 108.3
  
 5) NOTE: PLEASE BE SURE THE RELEVANT ELECTRICAL CODE AS
 SOPTED PER THE STATE IS ON PLANS.
 2005 NFPA-70 (NEC)
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  