Plan Review Notes
Plan Review Notes For Permit 07100454
Permit Number 07100454
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2007-11-15 15:50:11***DENIED***
  
 1) OK, PLEASE PROVIDE DIAGRAM ON FIRST FLOOR THAT
 IDENTIFIES THE LOCATION OF THE FIRE ALARM PANEL.
  
 2) THIS BUILDING APPEARS TO BE PROTECTED BY AN
 AUTOMATIC FIRE SPRINKLER SYSTEM. PLEASE PROVIDE
 APPLICABLE EQUIPMENT INFORMATION ON THE RISER DIAGRAM.
  
 3) FIRE ALARM TO BE CLASS A OR FULLY ADDRESSABLE. SYTEM
 SHALL BE UL CERTIFIED FOR CENTRAL STATION SERVICE IF
 SUPERVISING A FIRE SPRINKLER SYSTEM.
  
 NEW COMMENT:
  
 1) A MINIMUM OF TWO (2) SETS OF PLANS TO BE SUBMITTED
 FOR REVIEW.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW