Plan Review Notes For Permit 07100454 |
Permit Number |
07100454 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-11-15 15:50:11 | ***DENIED*** | | | | 1) OK, PLEASE PROVIDE DIAGRAM ON FIRST FLOOR THAT | | IDENTIFIES THE LOCATION OF THE FIRE ALARM PANEL. | | | | 2) THIS BUILDING APPEARS TO BE PROTECTED BY AN | | AUTOMATIC FIRE SPRINKLER SYSTEM. PLEASE PROVIDE | | APPLICABLE EQUIPMENT INFORMATION ON THE RISER DIAGRAM. | | | | 3) FIRE ALARM TO BE CLASS A OR FULLY ADDRESSABLE. SYTEM | | SHALL BE UL CERTIFIED FOR CENTRAL STATION SERVICE IF | | SUPERVISING A FIRE SPRINKLER SYSTEM. | | | | NEW COMMENT: | | | | 1) A MINIMUM OF TWO (2) SETS OF PLANS TO BE SUBMITTED | | FOR REVIEW. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|