2007-10-26 15:12:12 | ***DENIED*** | | | | 1) PLANS INDICATE THE INSTALLATION OF A FIRE ALARM | | PANEL. THE PANEL AND LOCATION IS NOT ILLUSTRATED ON THE | | DRAWINGS. IF EQUIPMENT IS LOCATED ON ANOTHER LEVEL, | | PLEASE ADVISE AND SUBMIT A DRAWING. | | | | 2) IT APPEARS THAT THE ALARM WILL SUPERVISE AN | | AUTOMATIC FIRE SPRINKLER SYSTEM. FIRE ALARM TO BE UL | | CERTIFIED FOR CENTRAL STATION SERVICE. | | | | 3) FIRE ALARM TO BE CLASS A OR FULLY ADDRESSABLE. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|