Plan Review Notes For Permit 07100424 |
Permit Number |
07100424 |
|
Review Stop |
B |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2008-07-23 11:24:19 | BUILDING PLAN REVIEW | | PERMIT: 07100424 | | ADD: 1641 WORTHINGTON ROAD #100 | | CONT: HEDRICK BROTHERS CONST. | | TEL: (561)389-2270 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | 7-23-08 | | REVIEW: REVISION | | ACTION: DENIED | | | | PROVIDE THE NEW ARCHITECTURAL SHEETS FOR SUITE #100 | | SHOWING ALL CHANGES. THERE ARE NEW MEP SHEETS SHOWING | | THE NEW LAYOUT; HOWEVER THE ARCHITECTURAL SHEETS WITH | | THE NEW CHANGES WERE NOT SUBMITTED. THE PLANS SUBMITTED | | ARE FOR THE FIRE SPRINKLER. PLEASE INDICATE THE CORRECT | | PERMIT NUMBER (07100424) ON THE RESUBMITTAL SHEET FOR | | EACH REVISION CONCERNING SUITE #100. | | 1)NOW THE FLOOR PLAN HAS BEEN ALTERED, THE MEP | | SHEETS AND ALL OTHER SHEETS SHALL MATCH THE NEW FLOOR | | PLAN SHOWING ALL THE CHANGES. A NEW SCHEMATIC FIRE | | SPRINKLER SHALL BE SUBMITTED TO OUR OFFICE SHOWING HOW | | THE NEW LAY OUT AFFECT THE SPRINKLER HEADS; THIS CAN BE | | SHOWN ON THE NEW CEILING PLANS PER FBC 106.1.5.1.1(5) | | AND FS 553.79(2) | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | (561)805-6726 | | [email protected] |
|