2008-07-23 11:24:19BUILDING PLAN REVIEW
 PERMIT: 07100424
 ADD: 1641 WORTHINGTON ROAD #100
 CONT: HEDRICK BROTHERS CONST.
 TEL: (561)389-2270
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 7-23-08
 REVIEW: REVISION
 ACTION: DENIED
  
 PROVIDE THE NEW ARCHITECTURAL SHEETS FOR SUITE #100
 SHOWING ALL CHANGES. THERE ARE NEW MEP SHEETS SHOWING
 THE NEW LAYOUT; HOWEVER THE ARCHITECTURAL SHEETS WITH
 THE NEW CHANGES WERE NOT SUBMITTED. THE PLANS SUBMITTED
 ARE FOR THE FIRE SPRINKLER. PLEASE INDICATE THE CORRECT
 PERMIT NUMBER (07100424) ON THE RESUBMITTAL SHEET FOR
 EACH REVISION CONCERNING SUITE #100.
 1)NOW THE FLOOR PLAN HAS BEEN ALTERED, THE MEP
 SHEETS AND ALL OTHER SHEETS SHALL MATCH THE NEW FLOOR
 PLAN SHOWING ALL THE CHANGES. A NEW SCHEMATIC FIRE
 SPRINKLER SHALL BE SUBMITTED TO OUR OFFICE SHOWING HOW
 THE NEW LAY OUT AFFECT THE SPRINKLER HEADS; THIS CAN BE
 SHOWN ON THE NEW CEILING PLANS PER FBC 106.1.5.1.1(5)
 AND FS 553.79(2)
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]