2007-10-25 14:32:52PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS, PER FBC/M
 403.2.
  
 2) NOTE: 1641 WORTHINGTON RD. IS A SHELL BUILDING.IT
 DOES NOT YET HAVE A CO SO THE SHELL BUILDING DESIGN
 PROFESSIONALS WILL BE REQUIRED TO PROVIDE A SHOP
 DRAWING REVIEW STAMP ON ANY BUILD-OUT PLANS THAT ARE
 PREPARED BY DIFFERENT DESIGNERS. SEE KAMM CONSULTING
 REVIEW NOTES DATED 9-17-07, PLEASE COMPLY.
  
 3)PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR THE
 ELECTRIC CEILING HEATERS (CH) AND MIT UNITS. PLEASE
 INDICATE WHICH UNITS ARE BEING INSTALLED IF NEEDED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]