2007-10-22 17:13:19 | *** DENIED *** |
| |
| ** PLEASE KNOW ONLY THREE SETS OF PLANS ARE NEEDED TO |
| BE SUBMITTED FOR REVIEW AND STAMPING. |
| AS THIS PROJECT CONTAINS A SPECIAL INSPECTOR THREE ARE |
| NEEDED BUT NOT FOUR SETS AS SUBMITTED. |
| |
| 1) NOTE: PLEASE SEE THE PERMIT APPLICATION NEEDS TO |
| CONTAIN THE SIGNATURE OF THE CONTRACTOR/QUALIFIER ON |
| THE BACK OF THE APPLICATION. PLEASE SEE THE SHEET IN |
| WHICH THE QUALIFIER SIGNED ON IS ACTUALLY A BLANK |
| PERMIT APPLICATION. |
| THE SECOND OTHER SIGNED SHEET IS SIGNED FROM AN |
| AUTHORIZED AGENT WHO IS NO LONGER CURRENT WITH THE |
| CITY. |
| PLEASE SUPPLY A NEW APPLICATION, OR UPDATE AUTHORIZED |
| AGENT WHO SIGNED ON SECOND PART OF APPLICATION. |
| (BENJAMIN CLEMENS IS CURRETNLY ON SECOND APPLICATION |
| SHEET ) |
| |
| 2) NOTE: PLEASE SHOW THE LOCATIONS OF THE FIRE ALARM |
| DEVICES TO MEET FBC FOR ADA COMPLIANCE. PLEASE BE SURE |
| THE LEVELS FOR HORNS/STROBES MEET THE MINIMUM LEVELS AS |
| REQUIRED. |
| PLEASE SEE FBC 11-4.28.1, .2, AND .3(4). |
| ** THIS IS REQUIRED ON THE BASE PLANS EVEN AS THE FIRE |
| ALARM IS UNDER SEPARATE PERMITS. |
| |
| 3) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| SHEETS FOR THE TANK-LESS WATER HEATER. |
| 110.3, 90.7. |
| PLEASE SEE 422.13 IF THIS UNIT IS A STORAGE TYPE WATER |
| HEATER, PLEASE BE SURE THE LOAD IS FIGURED AT 125%. |
| |
| 4) NOTE: PLEASE SEE THE PLANS INDICATE A STANDARD |
| LIGHTING SWITCH WHICH IS NOT PART OF THE LIGHTING |
| CONTROL LEGEND FOR AUTOMATED DEVICES. |
| PLEASE KNOW THAT MOST OF THE DEVICES ARE OK, HOWEVER |
| THE STANDARD SWITCHES AS LISTED ON THE PLANS NEEDS TO |
| BE CLARIFIED AND ADJUSTED TO MEET 13-415.1.ABC.1.1 AND |
| .1.2. |
| PLEASE SEE SECTION13-413.1.ABC.2.2 FOR REQUIRED |
| CONSTRUCTION DOCUMENTS AND NOTES ON PLANS. |
| |
| 5) NOTE: PLEASE SEE AS MENTIONED ON OTHER REVIEW FOR |
| BUILD OUTS BEING APPLIED FOR BEFORE THE CERTIFICATE OF |
| OCCUPANCY IS ISSUED ON THE BASED BUILDING. PLEASE KNOW |
| AS THE BUILDING IS STILL UNDER THE RESPONSIBILITY OF |
| THE BASE BUILDING DESIGN TEAM, ALL PLANS/SHEETS WILL BE |
| REQUIRED TO BE STAMPED WITH SOME SORT OF SHOP DRAWING |
| REVIEW STAMP OR BY OTHER MEANS WHICH WILL HAVE THE SAME |
| AFFECT.THIS MUST BE DONE FOR ALL TRADES WHETHER OR |
| NOT COMMENT IS MADE BY OTHER TRADES. |
| ** THIS CAN BE CONFIRMED WITH MR. ROBERT BROWN AND MR. |
| NEIL MELICK. |
| FS 471/481 |
| ** IT IS ALSO NOTED THAT THERE ARE LETTERS ATTACHED |
| FROM BASE BUILDING DESIGN TEAM WHICH INDICATE |
| COMMENTS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |