Plan Review Notes
Plan Review Notes For Permit 07100424
Permit Number 07100424
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-22 17:13:19*** DENIED ***
  
 ** PLEASE KNOW ONLY THREE SETS OF PLANS ARE NEEDED TO
 BE SUBMITTED FOR REVIEW AND STAMPING.
 AS THIS PROJECT CONTAINS A SPECIAL INSPECTOR THREE ARE
 NEEDED BUT NOT FOUR SETS AS SUBMITTED.
  
 1) NOTE: PLEASE SEE THE PERMIT APPLICATION NEEDS TO
 CONTAIN THE SIGNATURE OF THE CONTRACTOR/QUALIFIER ON
 THE BACK OF THE APPLICATION. PLEASE SEE THE SHEET IN
 WHICH THE QUALIFIER SIGNED ON IS ACTUALLY A BLANK
 PERMIT APPLICATION.
 THE SECOND OTHER SIGNED SHEET IS SIGNED FROM AN
 AUTHORIZED AGENT WHO IS NO LONGER CURRENT WITH THE
 CITY.
 PLEASE SUPPLY A NEW APPLICATION, OR UPDATE AUTHORIZED
 AGENT WHO SIGNED ON SECOND PART OF APPLICATION.
 (BENJAMIN CLEMENS IS CURRETNLY ON SECOND APPLICATION
 SHEET )
  
 2) NOTE: PLEASE SHOW THE LOCATIONS OF THE FIRE ALARM
 DEVICES TO MEET FBC FOR ADA COMPLIANCE. PLEASE BE SURE
 THE LEVELS FOR HORNS/STROBES MEET THE MINIMUM LEVELS AS
 REQUIRED.
 PLEASE SEE FBC 11-4.28.1, .2, AND .3(4).
 ** THIS IS REQUIRED ON THE BASE PLANS EVEN AS THE FIRE
 ALARM IS UNDER SEPARATE PERMITS.
  
 3) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE TANK-LESS WATER HEATER.
 110.3, 90.7.
 PLEASE SEE 422.13 IF THIS UNIT IS A STORAGE TYPE WATER
 HEATER, PLEASE BE SURE THE LOAD IS FIGURED AT 125%.
  
 4) NOTE: PLEASE SEE THE PLANS INDICATE A STANDARD
 LIGHTING SWITCH WHICH IS NOT PART OF THE LIGHTING
 CONTROL LEGEND FOR AUTOMATED DEVICES.
 PLEASE KNOW THAT MOST OF THE DEVICES ARE OK, HOWEVER
 THE STANDARD SWITCHES AS LISTED ON THE PLANS NEEDS TO
 BE CLARIFIED AND ADJUSTED TO MEET 13-415.1.ABC.1.1 AND
 .1.2.
 PLEASE SEE SECTION13-413.1.ABC.2.2 FOR REQUIRED
 CONSTRUCTION DOCUMENTS AND NOTES ON PLANS.
  
 5) NOTE: PLEASE SEE AS MENTIONED ON OTHER REVIEW FOR
 BUILD OUTS BEING APPLIED FOR BEFORE THE CERTIFICATE OF
 OCCUPANCY IS ISSUED ON THE BASED BUILDING. PLEASE KNOW
 AS THE BUILDING IS STILL UNDER THE RESPONSIBILITY OF
 THE BASE BUILDING DESIGN TEAM, ALL PLANS/SHEETS WILL BE
 REQUIRED TO BE STAMPED WITH SOME SORT OF SHOP DRAWING
 REVIEW STAMP OR BY OTHER MEANS WHICH WILL HAVE THE SAME
 AFFECT.THIS MUST BE DONE FOR ALL TRADES WHETHER OR
 NOT COMMENT IS MADE BY OTHER TRADES.
 ** THIS CAN BE CONFIRMED WITH MR. ROBERT BROWN AND MR.
 NEIL MELICK.
 FS 471/481
 ** IT IS ALSO NOTED THAT THERE ARE LETTERS ATTACHED
 FROM BASE BUILDING DESIGN TEAM WHICH INDICATE
 COMMENTS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]