2008-03-17 12:15:22PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLAN A-1 STATES "RELOCATE GAS DRYER" IF THE CLOTHES
 DRYER IS GAS THEN IT WOULD BE IN A CONFINED SPACE AND
 WILL REQUIRE COMBUSTION AND MAKE-UP AIR, PER 2004
 FBC/FG 304.1 AND 304.5.1. PLEASE CORRECT.
  
 2) AS NOTED IN LAST REVIEW 10-22-07 NOTE #3 PLEASE SHOW
 THE JOB ADDRESS IN THE TITLE BLOCK OF ALL PAGES, SEE
 WPB AMEND. 106.1.3.
  