2008-03-17 11:19:44 | ** DENIED2ND REVIEW** |
| |
| ** PLEASE SEE THE NOTES BELOW WHICH ARE FROM THE FIRST |
| REVIEW WHICH STILL NEED TO BE ADDRESSED. |
| |
| 1) NOTE: PLEASE SEE THE FOLLOWING CODES SHALL BE STATED |
| ON ELECTRICAL PLANS. |
| 2005 NFPA-70 |
| 2003 NFPA-101 |
| 2002 NFPA-72 |
| |
| 2) NOTE: PLEASE SUBMIT COMPLETE LAYOUT OF THE EXISTING |
| DWELLING SHOWING CURRENT CODE COMPLIANCE FOR SMOKE |
| ALARMS EXISTING OR NEW TO BE INSTALLED PER FBC R313 |
| NFPA-72 11.5.1.1.1, 11.8.3 |
| |
| 3) NOTE: PLEASE SEE 210.8A7 AS ALL RECEPTACLES |
| INCLUDING DEDICATED CIRCUITS WHICH ARE 15/20AMP 120V |
| WITHIN 6FT OF A LAUNDRY SINK SHALL BE GFI/GFI |
| PROTECTED. |
| |
| 4) NOTE: PLEASE SEE WATER HEATER BEING REPLACED DOES |
| NOT SHOW THE REQUIRED DISCONNECT PER 422.31 |
| |
| 5) NOTE: PLEASE INDICATE ON THE NEW PANEL SCHEDULES |
| SUBMITTED WHICH CIRCUITS ARE NEW AND WHICH ONES ARE |
| EXISTING. |
| FBC 106.3.5.4, NEC 408.4 |
| |
| |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |