Plan Review Notes
Plan Review Notes For Permit 07100395
Permit Number 07100395
Review Stop P
Sequence Number 1
Notes
Date Text
2007-10-31 08:51:24DENIED;
 1. ADD A DEMO.NOTE,NO DEAD ENDS PERMITED IN THE
 SANITARY SEWER SYSTEM MORE THAN 2'. FBC-2004 PLUMBING
 SECTION 704.5.
 2. PROVIDE A SANITARY RISER DIAGRAM. SHOW PIPE SIZES
 FOR DRAINAGE AND VENTS AND HOW BRANCH DRAIN WILL TIED
 INTO THE BUILDING SEWER. FBC-2004BUILDING CHAPTER 1
 SECTION 106.3.5.4(9).
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695