Plan Review Notes For Permit 07100395 |
Permit Number |
07100395 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-10-22 11:50:37 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) SEE YELLOW HIGH LIGHT ON MECHANICAL PLAN PAGE AC-1 | | TWO SUPPLY AIR DUCTS NEED TO BE SIZED (1EXIST. LAUN. | | ROOM & 1 NEW STOR.). | | | | 2) SHOW BATHROOM EXHAUST FAN ON MECHANICAL PLAN ALSO. | | SEE 2004 FBC/R R303.3 EXCEPT. | | | | 3) PLEASE SHOW THE JOB ADDRESS IN THE TITLE BLOCK, ALL | | PAGES, SEE WPB AMEND. 106.1.3. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|