2007-12-04 14:18:52 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS |
| TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| GAS PLAN REVIEW: |
| DENIED 2ND TIME: |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW ON THE RESUBMITTED DESIGNED CHANGED |
| PLANS TO MEET CODE COMPLIANCE: |
| |
| 1. TOTAL BTU'S FOR THE GAS SYSTEM OF 697,000 ARE |
| WRONG. THE CORRECT TOTAL BTU LOAD FOR THE GAS SYSTEM IS |
| 942,000. PLANS ARE INDICATING "NOTE: IN EMERGENCY WITH |
| NO POWER GENERATOR ONLY". HOW WILL THE OTHER APPLIANCES |
| BE SHUT OFF WHEN GENERATOR IS RUNNING? THERE IS NO |
| GUARANTEE THAT THIS WILL HAPPEN. PLEASE DELETE THAT |
| NOTE AND CORRECT THE TOTAL BTU'S TO THE SYSTEM ON THE |
| RESUBMITTAL. |
| |
| 2. THE GAS PIPING IS SIZED WRONG PER THE LONGEST |
| LENGTH OF 88 FEET (WHICH IS 90 FEET ON TABLES) AND FUEL |
| GAS TABLES 402.4 (2) AND 402.4(20). PLEASE REFERENCE |
| THE RED LINE CORRECTIONS TO THE GAS RISER AND THE GAS |
| TABLES ATTACHED TO THESE COMMENTS FOR THE RESUBMITTAL. |
| |
| |
| ********IMPORTANT INFORMATION******** |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED, PLEASE INCLUDE A |
| TRANSMITTAL LETTER INDICATING HOW EACH |
| ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. |
| NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| EXAMINER FOR REFERENCE FOR THE |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |