Plan Review Notes
Plan Review Notes For Permit 07100378
Permit Number 07100378
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-10-22 21:18:35*****APPROVED W/STIPULATION*****
  
  
 PLAN SHEET FP-1 STAMPED, INITIALED, AND DATED;READY
 FOR PERMIT ISSUANCE.
  
  
 PLEASE BE ADVISED, THAT AT THE TIME OF THE SPRINKLER
 HEAD INSPECTION,PROVIDE A LETTER TO THE FIRE
 INSPECTOR WITH THE LANGUAGE ON YOUR COMPANY LETTERHEAD
 STATING THAT THE 2-HOUR PRESSURE TESTAT 200 PSI
 CANNOT BE CONDUCTED AT THE PROJECT SITE AS PER THE
 EXCEPTION OF NFPA 13 - 2002 EDITION.THIS LETTER WILL
 BE ENTERED INTO THE FILES OF WEST PALM BEACH FIRE
 PREVENTION.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722