2007-10-26 16:05:05 | DENIED |
| REFERENCE: |
| ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS. |
| ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| REQUIREMENTS. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE (FAC). |
| ** FLORIDA STATUTES (FS). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| **NOTE: THE SUBMITTED DRAWING IS NOT AN ISOMETRIC AND |
| DOES NOT SHOW ALL CUT SECTIONS OF PIPE AND |
| CORRESPONDING LENGTHS. PLEASE CORRECT AND RESUBMIT. |
| |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| **NOTE: THE ONLY PIPING MATERIAL BEING INDICATED IS FOR |
| THE UNDERGROUND PE PIPE. WHAT IS THE ABOVE GROUND |
| PIPING MATERIAL? PLEASE CORRECT AND RESUBMIT. |
| |
| 3. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| **NOTE: PLEASE REFERENCE COMMENT #1 AND COMPLY ON THE |
| RESUBMITTAL. |
| |
| 4. PER FBC-2004 FUEL GAS SEC. 404.12 OUTLET CLOSURES: |
| GAS OUTLETS THAT DO NOT CONNECT TO APPLIANCES SHALL BE |
| CAPPED GAS TIGHT. |
| **NOTE: PLEASE INDICATE THIS FOR THE FUTURE BBQ AND |
| POOL HEATER ON THE RESUBMITTAL. |
| |
| 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| **NOTE: PLEASE SUBMIT MANUFACTURER SPECIFICATIONS FOR |
| THE MP REGULATORS INDICATING THE MAKE, MODEL NUMBER, |
| BTU LOAD CAPACITY, AND A LISTING FROM A NATIONALLY |
| RECOGNIZED TESTING LABORATORY. |
| |
| 6. THE VALUE OF $450.00 SEEMS TO LOW PER FBC-2004, |
| CHAPTER 1, SECTION |
| 108.3, BUILDING PERMIT VALUATION: IF IN |
| THE OPINION OF THE BUILDING OFFICIAL, |
| THE CLAIMED VALUATION OF THE BUILDING, |
| ALTERATION, STRUCTURE, ELECTRICAL, GAS |
| MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| TO BE UNDERESTIMATED ON THE APPLICATION, |
| THE PERMIT SHALL BE DENIED. FOR |
| PERMITTING PURPOSES, VALUATION OF |
| BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| FINISH, NORMAL SITE WORK (EXCAVATION AND |
| BACKFILL FOR BUILDINGS), ARCHITECTURAL |
| AND DESIGN FEES, MARKETING COSTS, |
| OVERHEAD AND PROFIT; EXCLUDING ONLY LAND |
| VALUE. VALUATION REFERENCES MAY INCLUDE |
| THE LATEST PUBLISHED DATA OF NATIONAL |
| CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| MEANS ECT.) WITH |
| REGIONAL ADJUSTMENTS FOR LOCATION AS |
| PUBLISHED BY INTERNATIONAL CODE |
| CONGRESS. |
| **NOTE: PLEASE ADJUST THE VALUE ON THE PERMIT |
| APPLICATION PRIOR TO THE RESUBMITTAL AND PAY FEES IF |
| APPICABLE OR PROVIDE A COPY OF THE SIGNED CONTRACT THAT |
| REFLECTS THE INDICATED VALUE ON THE PERMIT |
| APPLICATION. |
| |
| 7. FBC-2004 CHAPTER 1,SECTION 106.3.4.3: |
| THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| NAME, AND ALSO DATE DRAWING. PLEASE DO |
| THIS PRIOR TO RESUBMITTING. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY: MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL: [email protected] |