Plan Review Notes
Plan Review Notes For Permit 07100340
Permit Number 07100340
Review Stop G
Sequence Number 1
Notes
Date Text
2007-10-25 13:37:56DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ***NOTE: NOT ALL CORRESPONDING LENGTHS ARE INDICATED
 FOR ALL CUT SECTIONS OF PIPE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 ***NOTE: NOT ALL PIPE SIZES OR MATERIALS ARE INDICATED.
 PLEASE CLARIFY IF THE 8' RISER OF 1" POLY U/G IS
 MISLABELED, SHOULDN'T IT BE 8' OF 1" GALV. A/G. PLEASE
 BE AWARE THAT THE 199,000 BTU WATER HEATER NEEDS TO BE
 1-1/4" SCH. 40 METALLIC PER TABLE 402.4 (2) WITH THE
 99' DEVELOPED LENGTH.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ***NOTE: PLEASE REFERENCE COMMENT #1. PLEASE KNOW THAT
 SYSTEM IS NOW SIZED WITH TABLES USING A LONGEST LENGTH
 OF 100'. IF COMMENT #1 CHANGES THE DEVELOPED LENGTH AS
 BEING OVER 100', THE SYSTEM WILL NEED TO BE RESIZED.
  
 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ***NOTE:THE SUBMITTED MANUFACTURER SHEETS FOR THE
 FOLLOWING APPLIANCES NEED THE FOLLOWING INFORMATION ON
 THE RESUBMITTAL.
  
 **A} ISOKERN UNVENTED GAS LOG:
 A) VERIFICATION OF THE APPLIANCE BTU LOAD.
 B) VERIFICATION THAT THE APPLIANCE IS LISTED BY A
 NATIONALLY RECOGNIZED TESTING LABORATORY.
  
 **B} JENN-AIR RANGE:
 A) VERIFICATION OF THE APPLIANCE BTU LOAD.
  
 5. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
 ***NOTE: THE GAS RISER AND PLAN-SHOP DRAWINGS HAS
 GORDON F. BUCK OF BUCK ENGINEERING AS HAVING REVIEWED
 THE DRAWINGS BUT IS NOT TAKING THE RESPONSIBILITY OF
 THE DRAWINGS. SOMEONE NEEDS TO TAKE THE RESPONSIBILITY
 FOR THE DESIGN ON THE RESUBMITTAL.
  
 6. NOTE: SHEET 3.1 IS A REVISION FOR MASTER PERMIT
 #07020398 AND MUST BE SUBMITTED AS SUCH PER FBC-2004
 CHAPTER 1, SECTION 106.4, AMENDED CONSTRUCTION
 DOCUMENTS. THIS SHEET WILL NOT BE REVIEWED ON THIS
 PERMIT APPLICATION.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]