2008-07-03 14:36:05PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLAN
 *** DENIED ***
  
 1) REVISED MECHANICAL PLAN NEEDS TO BE SIGNED AND
 SEALED BY THE ENGINEER (JAMES MINGES), PER FAC
 61G1-16.003.
  
 2) PROVIDE FOR RETURN AIR TO THE THREE BEDROOMS, PER
 2004 FBC/R M1602.4.
  
 3) EQUIPMENT SCHEDULE SHOWS THE SYSTEM AS A 12 SEER,
 PER 2004 FBC 13-607.1.ABC.3.2.1 THE MINIMUM SEER IS 13.
 PLEASE CORRECT.
  
 4) THE SUITE NUMBERFOR THIS UNIT IS 103 ACCORDING TO
 CITY RECORDS, PLANS SHOW THE SUITE NUMBER CHANGED TO
 203. PLEASE CORRECT.
  
 5) PLAN SHOWS ONE 8" SUPPLY AIR DUCT FEEDING TWO 8"
 DUCTS AND THREE 4" DUCTS. THIS DESIGN DOES NOT COMPLY
 WITH ACCA MANUAL D STANDARDS, PLEASE CORRECT OR SUBMIT
 YOUR MANUAL D CALCULATIONS, PER 2004 FBC/R M1601.1.
  
 6) PLEASE SHOW THE SIZES OF ALL GRILLS ON THE
 MECHANICAL PLAN, PER 2004 WPB AMEND. 106.3.5.4 (10).
  
 7) SHOW THE SIZE OF THE MAIN SUPPLY AIR TRUNK LINE ON
 THE MECHANICAL PLAN, PER 2004 WPB AMEND. 106.5.4.3
 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729