Plan Review Notes
Plan Review Notes For Permit 07100318
Permit Number 07100318
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-02-11 09:44:05*****DENIED*****
  
  
 1.THE NUMERICAL ADDRESS SHOWN IN THE TITLE BLOCK OF
 THE SUBMITTED PLAN SHEETS DOES NOT CORRELATE WITH THE
 APPLICATION OR WHAT IS LISTED IN OUR SYSTEM.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 4.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 5.IT IS SHOWN ON THE FLOOR PLAN THAT THE DWELLING
 UNIT HAS SMOKE DETECTORS.BE ADVISED THAT SMOKE
 DETECTORS ARE TIED INTO A BUILDING'S FIRE ALARM SYSTEM;
 WHEREAS SMOKE ALARMS SHALL SOUND ONLY WITHIN AN
 INDIVIDUAL DWELLING UNIT AND SHALL NOT ACTUATE THE
 BUILDING FIRE ALARM.PLEASE INDICATE AS TO WHICH
 DEVICE IS BEING USED.
  
 6.PLEASE EXPLAIN THE CLOSE PROXIMITY (SPACING) OF THE
 TWO SMOKE DETECTORS/SMOKE ALARMS IN THE LIVING ROOM
 JUST OUTSIDE OF BEDROOM #3.
  
 7.SPECIFY THE INTERIOR FINISH MATERIAL FOR THE NEW
 WALL IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722