2008-01-22 14:23:13 | |
| |
| ** DENIEDREVIEW ** |
| |
| 1) NOTE: PLEASE SEE THE FOLLOWING CODES SHALL BE STATED |
| ON PLANS FOR RELEVANT DESIGN. |
| FBC 2004 W/2007 REVISIONS. |
| 2005 NFPA-70 |
| 2003 NFPA-101 |
| 2002 NFPA-72 |
| |
| 2) NOTE: PLEASE SEE FS 481.219 FOR POSSIBLE FICTITIOUS |
| NAME FOR ARCHITECT. |
| PLEASE COMPLETE INFORMATION ON TITLE BLOCKS PER FAC |
| 61G1-16.004 |
| |
| 3) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND |
| CORRELATE WITH THE PANEL SCHEDULE. |
| PLEASE SEE 240.4, 310.16, 408.4 |
| FBC 106.3.5.1.2 (ADDITIONAL INFORMATION). |
| |
| 4) NOTE: PLEASE SEE SOME CIRCUITS ON PANEL SCHEDULE AS |
| SHOWN DO NOT COMPLY WITH THE NEC. FOR EXAMPLE: PLEASE |
| SEE WATER HEATER WHICH IS SHOWN AS 4500VA LOAD YET THIS |
| IS ONLY SHOWN ON A SINGLE POLE 25AMP BRANCH CIRCUIT. |
| PLEASE SEE 422.13, 240.4, 310.16 ETC |
| |
| 5) NOTE: PLEASE SEE NFPA-72 FOR DEFINITIONS OF SMOKE |
| DETECTION DEVICES. |
| PLEASE SEE THE PLANS CALL FOR *SMOKE DETECTORS* AND BY |
| DEFINITION THIS WOULD MEAN THESE ARE PART OF A FIRE |
| ALARM SYSTEM. SMOKE DETECTORS ONLY DETECT AND DO NOT |
| SOUND WARNING. PLEASE SEE BASED ON PLANS AND PANEL |
| SCHEDULE IT SEEMS THESE ARE *SMOKE ALARMS* WHICH |
| ACTUALLY DETECT AND SOUND AND ALARM. |
| PLEASE CLARIFY AND COMPLETE. |
| |
| 6) NOTE: PLEASE SEE 210.12 AS ARC FAULT PROTECTION IS |
| REQUIRED FOR ALL BRANCH CIRCUITS/OUTLETS IN SLEEPING |
| ROOMS. |
| PLEASE SEE ONLY ONE BRANCH CIRCUIT FOR SMOKE DETECTION |
| TYPE DEVICES SHOWS AFCI BREAKER. |
| PLEASE ADJUST AND LIST ALL CIRCUITS REQUIRED. |
| |
| 7) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.53 FOR |
| SMALL APPLIANCE CIRCUITS ALONG WITH DINING AREAS AND |
| AREAS OF THE LIKE. |
| |
| 8) NOTE: PLEASE CLARIFY IF THE PANEL SHOWN ON PLANS IS |
| NEW OR ALREADY EXIST? SHOWN ON PLANS AS NEW YET NO |
| CONDUCTORS FOR NEW OR EXISTING FEEDERS IS SHOWN. |
| 240.4, 310.16 ETC |
| |
| 9) NOTE: PLEASE SEE NFPA-72 11.8.3 FOR SMOKE DETECTION |
| DEVICE LOCATIONS. PLEASE SEE NO DEVICES SHALL BE WITHIN |
| 3FT OF DOORS TO BATHROOMS. |
| PLEASE SEE OTHER REQUIRED DISTANCES AND ALSO SPECIFIC |
| REQUIREMENTS PER THE MANUFACTURE. |
| 110.3 |
| |
| 10) NOTE: PLEASE SEE 210.11C3 FOR MISSING DEDICATED |
| BATH CIRCUIT(S). |
| MUST BE 20AMP AND #12. |
| |
| ** PLEASE COMPLETE THE ABOVE AND KNOW AS THERE IS |
| INFORMATION NOT YET SHOWN A COMPLETE REVIEW FOR CODE |
| COMPLIANCE CAN NOT BE DONE AT THIS TIME. |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |