2008-03-14 09:14:08 | ** DENIED2RD REVIEW ** |
| |
| ** PLEASE SEE THE NOTES BELOW WHICH ARE FROM THE FIRST |
| REVIEW WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW |
| COMMENTS DUE TO INFORMATION NOW BEING ADDED TO PLANS. |
| |
| |
| 1) NOTE: PLEASE SEE THE RISER WHICH SHOWS NO OCP FOR |
| PANEL. |
| 230.70, 230.71. IS THIS A METER CENTER? |
| |
| 2) NOTE: PLEASE SEE THE RISER SHOWS 3-#3, 1#8 AND |
| ANOTHER #8? WHAT IS THIS SECOND #8? |
| PLEASE CLARIFY. |
| 230, 215, 310 |
| FBC 106.1.2 |
| |
| 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE WITH RESPECT |
| TO 210.11C1, 210.52B1 AND 220.52 AS ONE OR MORE OF THE |
| SMALL APPLIANCE, DINING ROOM RECEPTACLE CIRCUITS ETC |
| ARE REQUIRED TO BE FIGURED AT 1500VA. PLEASE SEE LOAD |
| CALCULATIONS ONLY SHOW THE TWO SMALL APPLIANCE |
| CIRCUITS. |
| |
| 4) NOTE: PLEASE SEE THE CU IS BEING SHOWN ON A 1-POLE |
| 20AMP CIRCUIT.HOW CAN THIS BE CORRECT WITH A 2.5 TON |
| CU.THE MODEL AS GIVEN BY THE MANUFACTURE STATES A |
| MINIMUM OF 230V. |
| PLEASE ADJUST. |
| 240.4, 310.16, 408.4, 110.3, 90.7 |
| FBC 106.1.2 |
| |
| 5) NOTE: PLEASE SEE KITCHEN COUNTER WHICH REQUIRES GFI |
| WITHIN 2FT OF THE END OF COUNTER SPACE. |
| PLEASE ALSO SEE THE DISPOSAL IN KITCHEN DOES NOT SHOW |
| ANY METHOD FOR CONTROL. WILL THIS BE SELF ACTUATING? |
| 210.52C1 |
| FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| |
| 6) NOTE: PLEASE SEE 424.3B WHICH REQUIRES OCP FOR HEAT |
| IN AHU TO BE SIZED AT 125%. PANEL SHOWS 40AMP OCP. MIN |
| PER SECTION OF CODE GIVEN SHOULD BE 45AMPS. |
| THE SIZING OF BRANCH-CIRCUIT CONDUCTORS AND |
| OVER-CURRENT DEVICES SUPPLYING FIXED ELECTRIC |
| SPACE-HEATING EQUIPMENT AT 125 PERCENT OF THE TOTAL |
| LOAD OF THE HEATERS (AND MOTORS) IS PREDICATED ON THE |
| NEED TO PROTECT OVER-CURRENT DEVICES, PARTICULARLY IN |
| PANEL-BOARDS, AND CONDUCTORS FROM OVERHEATING DURING |
| PERIODS OF PROLONGED OPERATION. |
| ** THIS ALSO AFFECT FEEDERS AND LOAD CALCULATIONS. |
| |
| 7) NOTE: PLEASE GO OVER LOAD CALCULATIONS. BASED ON |
| COMMENTS ABOVE THE LOAD WILL BE INCREASING DUE TO SOME |
| ITEMS MISSING. |
| PLEASE ALSO SEE LOADS SUCH AS DISPOSAL WHICH IS BEING |
| SHOWN AS 1500VA ON PANEL SCHEDULE AND 1000VA ON LOAD |
| CALCULATIONS. WHAT HAPPENED TO THE OTHER 500VA? PLEASE |
| SEE 422.13 AS THIS SPECIFICALLY IDENTIFIES AN ELECTRIC |
| WATER HEATER WITH A STORAGE CAPACITY OF 120 GAL OR LESS |
| AS A CONTINUOUS LOAD. THIS REVISION REQUIRES THE BRANCH |
| CIRCUIT OVERCURRENT DEVICE AND CONDUCTORS TO BE SIZED |
| BASED ON 125 PERCENT OF THE WATER HEATER NAMEPLATE |
| RATING UNLESS THE OVERCURRENT DEVICE AND THE ASSEMBLY |
| IT IS INSTALLED IN ARE LISTED TO BE USED AT 100 PERCENT |
| OF ITS CONTINUOUS CURRENT RATING. IN ADDITION, FEEDERS |
| AND SERVICES THAT SUPPLY WATER HEATER BRANCH CIRCUITS |
| ARE ALSO IMPACTED BY THE FACT THAT THIS TYPE OF |
| EQUIPMENT IS CONSIDERED TO BE A CONTINUOUS LOAD. |
| AS THE LOAD ON THE SERVICE PANEL IS SHOWN VERY CLOSE TO |
| BEING OVERLOADED THERE IS CONCERN OVER THE SIZE. 220, |
| 215 ETC |
| FBC 106.3.5.1.2, 106.1.2 |
| |
| 8) NOTE: PLEASE SEE SPECIFIC NOTES ON PREVIOUS REVIEW |
| AND ALOGN WITH FBC AND FS REQUIRES THE CODE ADOPTED AND |
| UNDER DESIGN FOR ANY PROJECT TO BE STATED ON PLANS |
| ALONG WITH LEVEL OF ALTERATION. |
| FS 553.73 |
| CODES WERE ADDED HOWEVER NOT YEAR EDITION AS GIVEN ON |
| PREVIOUS REVIEW. |
| 2005 NFPA70 |
| 2003 NFPA_101 |
| 2002 NFPA-72 |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |