Plan Review Notes
Plan Review Notes For Permit 07100317
Permit Number 07100317
Review Stop E
Sequence Number 2
Notes
Date Text
2008-03-14 09:14:08** DENIED2RD REVIEW **
  
 ** PLEASE SEE THE NOTES BELOW WHICH ARE FROM THE FIRST
 REVIEW WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW
 COMMENTS DUE TO INFORMATION NOW BEING ADDED TO PLANS.
  
  
 1) NOTE: PLEASE SEE THE RISER WHICH SHOWS NO OCP FOR
 PANEL.
 230.70, 230.71. IS THIS A METER CENTER?
  
 2) NOTE: PLEASE SEE THE RISER SHOWS 3-#3, 1#8 AND
 ANOTHER #8? WHAT IS THIS SECOND #8?
 PLEASE CLARIFY.
 230, 215, 310
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE WITH RESPECT
 TO 210.11C1, 210.52B1 AND 220.52 AS ONE OR MORE OF THE
 SMALL APPLIANCE, DINING ROOM RECEPTACLE CIRCUITS ETC
 ARE REQUIRED TO BE FIGURED AT 1500VA. PLEASE SEE LOAD
 CALCULATIONS ONLY SHOW THE TWO SMALL APPLIANCE
 CIRCUITS.
  
 4) NOTE: PLEASE SEE THE CU IS BEING SHOWN ON A 1-POLE
 20AMP CIRCUIT.HOW CAN THIS BE CORRECT WITH A 2.5 TON
 CU.THE MODEL AS GIVEN BY THE MANUFACTURE STATES A
 MINIMUM OF 230V.
 PLEASE ADJUST.
 240.4, 310.16, 408.4, 110.3, 90.7
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE KITCHEN COUNTER WHICH REQUIRES GFI
 WITHIN 2FT OF THE END OF COUNTER SPACE.
 PLEASE ALSO SEE THE DISPOSAL IN KITCHEN DOES NOT SHOW
 ANY METHOD FOR CONTROL. WILL THIS BE SELF ACTUATING?
 210.52C1
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 6) NOTE: PLEASE SEE 424.3B WHICH REQUIRES OCP FOR HEAT
 IN AHU TO BE SIZED AT 125%. PANEL SHOWS 40AMP OCP. MIN
 PER SECTION OF CODE GIVEN SHOULD BE 45AMPS.
 THE SIZING OF BRANCH-CIRCUIT CONDUCTORS AND
 OVER-CURRENT DEVICES SUPPLYING FIXED ELECTRIC
 SPACE-HEATING EQUIPMENT AT 125 PERCENT OF THE TOTAL
 LOAD OF THE HEATERS (AND MOTORS) IS PREDICATED ON THE
 NEED TO PROTECT OVER-CURRENT DEVICES, PARTICULARLY IN
 PANEL-BOARDS, AND CONDUCTORS FROM OVERHEATING DURING
 PERIODS OF PROLONGED OPERATION.
 ** THIS ALSO AFFECT FEEDERS AND LOAD CALCULATIONS.
  
 7) NOTE: PLEASE GO OVER LOAD CALCULATIONS. BASED ON
 COMMENTS ABOVE THE LOAD WILL BE INCREASING DUE TO SOME
 ITEMS MISSING.
 PLEASE ALSO SEE LOADS SUCH AS DISPOSAL WHICH IS BEING
 SHOWN AS 1500VA ON PANEL SCHEDULE AND 1000VA ON LOAD
 CALCULATIONS. WHAT HAPPENED TO THE OTHER 500VA? PLEASE
 SEE 422.13 AS THIS SPECIFICALLY IDENTIFIES AN ELECTRIC
 WATER HEATER WITH A STORAGE CAPACITY OF 120 GAL OR LESS
 AS A CONTINUOUS LOAD. THIS REVISION REQUIRES THE BRANCH
 CIRCUIT OVERCURRENT DEVICE AND CONDUCTORS TO BE SIZED
 BASED ON 125 PERCENT OF THE WATER HEATER NAMEPLATE
 RATING UNLESS THE OVERCURRENT DEVICE AND THE ASSEMBLY
 IT IS INSTALLED IN ARE LISTED TO BE USED AT 100 PERCENT
 OF ITS CONTINUOUS CURRENT RATING. IN ADDITION, FEEDERS
 AND SERVICES THAT SUPPLY WATER HEATER BRANCH CIRCUITS
 ARE ALSO IMPACTED BY THE FACT THAT THIS TYPE OF
 EQUIPMENT IS CONSIDERED TO BE A CONTINUOUS LOAD.
 AS THE LOAD ON THE SERVICE PANEL IS SHOWN VERY CLOSE TO
 BEING OVERLOADED THERE IS CONCERN OVER THE SIZE. 220,
 215 ETC
 FBC 106.3.5.1.2, 106.1.2
  
 8) NOTE: PLEASE SEE SPECIFIC NOTES ON PREVIOUS REVIEW
 AND ALOGN WITH FBC AND FS REQUIRES THE CODE ADOPTED AND
 UNDER DESIGN FOR ANY PROJECT TO BE STATED ON PLANS
 ALONG WITH LEVEL OF ALTERATION.
 FS 553.73
 CODES WERE ADDED HOWEVER NOT YEAR EDITION AS GIVEN ON
 PREVIOUS REVIEW.
 2005 NFPA70
 2003 NFPA_101
 2002 NFPA-72
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]