Plan Review Notes
Plan Review Notes For Permit 07100317
Permit Number 07100317
Review Stop B
Sequence Number 2
Notes
Date Text
2008-01-30 16:54:35PROJECT: 1801 CONSULATE PLACE #201
  
 CODE REVIEW:
 2004 FLORIDA EXISTING BUILDING CODE W/2006 REVISIONS
 2004 FLORIDA BUILDING CODE W/ 2006 REVISIONS
 CITY OF WEST PALM BEACH ADMINISTRATION AMENDMENTS,
 CHAPTER 1, 2004 EDITION
  
 STATUS: FAILED
  
 COMMENTS:
  
 1) REQUIRE A NOTICE OF COMMENCEMENT AS PER THE
 FOLLOWING:
  
 FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2) PLEASE INDICATE THE LEVEL OF ALTERATION AS PER THE
 FOLLOWING:
  
 FLORIDA EXISTING BUILDING CODE, SECTION301.5 :A
 DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR A
 COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO SECTION 303,304 & 305
 OF THIS CODE.
  
 3) PLEASE INDICATE ON FLOOR PLAN:NEW WALLS/EXISTING
 WALLS.
  
 4) PLEASE PROVIDE PRODUCT APPROVALS FOR THE INDICATED
 SLIDING GLASS DOORS.
  
 5) THE PRESCRIPTIVE FIRE RESISTANCE INDICATED ON THE
 TWO HOUR RATED WALL DOES NOT REFLECT THE DATA SHOWN BY
 TABLE 720.1(2)#13-1.3.
 PLEASE CORRECT THE SAME OR INDICATE A TESTED AND
 APPROVED RATED ASSEMBLY.
  
 6) PLEASE PROVIDE INTERIOR DIMENSIONS AND SQUARE
 FOOTAGE.
  
 7) PLEASE PROVIDE ENERGY CALCULATIONS AS PER THE
 FOLLOWING:
  
 512.1MINIMUM REQUIREMENTS.
 ALTERATIONS SUBJECT TO THIS CHAPTER SHALL COMPLY WITH
 THE REQUIREMENTS OF CHAPTER 13 OF THE FLORIDA BUILDING
 CODE, BUILDING.
  
 END COMMENTS
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
 E-MAIL: KCONRAD @WPB.ORG