Plan Review Notes For Permit 07100317 |
Permit Number |
07100317 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-01-18 14:34:31 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) THE NAME IN THE TITLE BLOCK "BLUE MINGES ARCHITECT" | | IS A FICTITIOUS NAME AND AS A FIRMS NAME WOULD REQUIRE | | A CERTIFICATE OF AUTHORIZATION, SEE F.S. 481.219 (2). | | PLEASE CORRECT. | | | | 2) PLEASE SHOW THE RETURN DUCT (FLEX) AND SIZE TO BED | | #1 AND BED #2, SEE 2004 FBC 106.3.5. | | | | 3) THE RETURN AIR GRILL IN BED #3 IS SHOWN AS A SUPPLY | | GRILL, PLEASE CORRECT. | | | | 4) PERMIT APPLICATION IS MISSING FROM PLANS, PLEASE | | SUBMIT A PERMIT APPLICATION WITH CONTRACTOR SIGNED ON. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|