2008-02-11 11:06:32 | *****DENIED***** | | | | | | 1.ONLY ONE PLAN SET WAS SUBMITTED;TWO OR MORE SETS | | SHALL BE PERMITTED WITH EACH APPLICATION. | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | 4.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | REFERENCED. | | | | 5.IT IS SHOWN ON THE FLOOR PLAN THAT THE DWELLING | | UNIT HAS SMOKE DETECTORS.BE ADVISED THAT SMOKE | | DETECTORS ARE TIED INTO A BUILDING'S FIRE ALARM SYSTEM; | | WHEREAS SMOKE ALARMS SHALL SOUND ONLY WITHIN AN | | INDIVIDUAL DWELLING UNIT AND SHALL NOT ACTUATE THE | | BUILDING FIRE ALARM.PLEASE INDICATE AS TO WHICH | | DEVICE IS BEING USED. | | | | 6. SPECIFY THE INTERIOR FINISH MATERIAL FOR THE NEW | | WALL IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS | | ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|